Page
12
Start-Up Tests
A. Testing the Control Wiring and Service Switches
1.
Turn the control switch to the
ON
position. Voltage should read 120 VAC. If it does not, consult an
electrician before continuing this testing.
2.
From the System Enable Screen (Refer to Users Guide) turn the first service button to the
ON
Position.
3.
The button will turn green and the corresponding LED on the PLC will illuminate.
Using testing probes, verify that the corresponding terminal posts at Terminal 2 are energized.
4.
Repeat steps 2 and 3 for the remainder of the service switches.
5.
Turn all service switches
ON
. All services should be
ON
. All green indicating lights should be
illuminated. Verify
ALL
power loads with test probe.
6.
Turn service switches
OFF
.
B.
Testing the Panic Button
1.
If the unit is integrated with a monitoring system:
a.
Press and release the red Panic Button.
b.
Verify that all Solenoids have been deactivated.
2.
Press the Reset System button on the screen.
NOTE:
Electrical Service will not shut down with Panic Button. Electrical Service will only shut down
with seismic activity.
C. Testing the Building Alarm Input signal
The unit has been factory tested to assure that the “Alarm” Input perform correctly. Field verify that
wiring to Terminal 1 is connected to the proper posts.
D. Testing the Building’s Utility Systems
1.
Turn
ALL
control switches
ON
.
2.
Field-test
ALL
utility and appliance outlets to confirm that services have become active.
3.
Turn the switch for each utility to
OFF
. Verify that the specific utility outlets are not active or “
ON
”.
E. Test Completion
The unit should now be fully operable. If it is not, contact an
ISIMET
Service Representative.
1.
Turn the Control Switch
OFF
.
2.
Reconnect
ALL
integrated services.
3.
Replace
ALL
panels and covers.
4.
Turn the Control Switch
ON
.
5.
Close and lock the Door Panel.
Содержание RLA Series
Страница 5: ...Page 5...