background image

Page 

12

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 Start-Up Tests 

 
A.  Testing the Control Wiring and Service Switches 

1.

 

Turn the control switch to the 

ON

 position. Voltage should read 120 VAC.  If it does not, consult an 

electrician before continuing this testing. 

2.

 

From the System Enable Screen (Refer to Users Guide) turn the first service button to the 

ON

 Position. 

3.

 

The button will turn green and the corresponding LED on the PLC will illuminate. 
Using testing probes, verify that the corresponding terminal posts at Terminal 2 are energized.  

4.

 

Repeat steps 2 and 3 for the remainder of the service switches. 

5.

 

Turn all service switches 

ON

. All services should be 

ON

. All green indicating lights should be 

illuminated. Verify 

ALL

 power loads with test probe. 

6.

 

Turn service switches 

OFF

 
B.

 

Testing the Panic Button 

1.

 

If the unit is integrated with a monitoring system: 
a.

 

Press and release the red Panic Button.   

b.

 

Verify that all Solenoids have been deactivated. 

2.

 

Press the Reset System button on the screen.   

 
NOTE:

 Electrical Service will not shut down with Panic Button. Electrical Service will only shut down 

with seismic activity. 
 

C.  Testing the Building Alarm Input signal 

The unit has been factory tested to assure that the “Alarm” Input perform correctly.  Field verify that      
wiring to Terminal 1 is connected to the proper posts. 

 

D.  Testing the Building’s Utility Systems 

1.

 

Turn 

ALL

 control switches 

ON

2.

 

Field-test 

ALL

 utility and appliance outlets to confirm that services have become active. 

3.

 

Turn the switch for each utility to 

OFF

.  Verify that the specific utility outlets are not active or “

ON

”. 

 
E.  Test Completion 

The unit should now be fully operable.  If it is not, contact an 

ISIMET

 Service Representative. 

1.

 

Turn the Control Switch 

OFF

2.

 

Reconnect 

ALL

 integrated services. 

3.

 

Replace 

ALL

 panels and covers. 

4.

 

Turn the Control Switch 

ON

5.

 

Close and lock the Door Panel. 

Содержание RLA Series

Страница 1: ...3 Residential Water Leak Detection RLA 3 Installation Maintenance Operations and Start up Instructions Read all instructions BEFORE installation and USE of Controller KEEP INSTRUCTIONS FOR FUTURE USE...

Страница 2: ...d monitoring systems The system should be thoroughly tested and adjustments made at time of initial operation Periodic testing should be conducted by the user to assure that all components function an...

Страница 3: ...nnecting Controlled Services 10 Battery Backup 10 Connecting Alarm Monitoring Wiring 11 Start Up Checklist 11 Start Up Test Preliminary Information 11 Start Up Test 12 Equipment Operation 13 Troublesh...

Страница 4: ...be confirmed prior to installation Enclosed with this Manual is a separate registration form The front of the form is for equipment warranty registration The back is a copy of the equipment start up c...

Страница 5: ...Page 5...

Страница 6: ...n time to ensure that this occurs A Flush Mounting Trim Flange is provided with each flush mounted unit Separate installation instructions and hardware are included with this flange Semi and Flush Tri...

Страница 7: ...e followed when connecting the conduit to the service panel Figure 4 Controller Knock out holes Wiring the RLA Controller Important Verify that the electrical supply is disconnected prior to connectin...

Страница 8: ...extend lock position STEP 4 Installing Flush Door Trim Figure 7 Prior to installing Door Trim ensure that wall finishes are complete and that the door panel has been installed To install the Flush Doo...

Страница 9: ...escription of Status When Light is On PWR PLC has 24VDC from Power Supply RUN PLC is set to RUN Mode and is operational ERR PLC Processor has incurred an error X1 Door Panic Button is being pressed X2...

Страница 10: ...ctly to the Output Terminal in order to function as intended Connect Supply Solenoid to the ON w Latch Terminals Make connections to BLK and WHT pins to match instructions provided with the solenoids...

Страница 11: ...ct short or input voltage at the output circuit will cause damage to the PLC and Controller Verify that the Door Panel plug is firmly secured to its terminal and ground wire is connected Examine Door...

Страница 12: ...ing system a Press and release the red Panic Button b Verify that all Solenoids have been deactivated 2 Press the Reset System button on the screen NOTE Electrical Service will not shut down with Pani...

Страница 13: ...l breakage in piping or circuits may cause damage to the facility Integral time delay programming insures that brief seismic or similar activity will not affect services To Activate One or More of the...

Страница 14: ...l In many cases failure of the system is the result of improper connection of a remote service or device such as a remote relay solenoid or building alarm system Refer to Equipment Specifications to c...

Страница 15: ...all moisture is removed from the compartment The electronic controller PLC is sensitive to moisture dust debris and other air borne particles Do not expose the interior compartment of the enclosure Du...

Страница 16: ...not specifically intended for use in applications where a master shut down and re instate device is located away from areas of normal use ISIMET s opinion is that in such cases there is risk that the...

Отзывы: