Figure 3
Figure 5 - Junction Box
Installing the Electrical Conduit
Only one Knock-Out is provided from the factory on the top left corner of the RLA Controller.
Connect rigid conduit for the required 120 VAC electrical service at the top left as indicated in
Figure 4.
Conduit holes for wiring to Terminals 1 & 2 may be made on the top, bottom, or right side of the enclosure.
Important!
All local codes must be followed when connecting the conduit to the service panel.
Figure 4 – Controller
Knock-out
holes
Wiring the RLA Controller
Important!
Verify that the electrical supply is disconnected prior to
connecting wiring to the RLA Controller.
To wire the RLA Controller:
1.
Remove the junction box cover from the panel
surface.
2.
Make final connections to the 120 VAC electrical
service to wiring within the junction box. Verify that
line wiring (Black), neutral (White), and ground wire
(Green) are correctly connected. Minimum
recommended wire size is 14 AWG.
3.
Replace the junction box cover before activating or
testing the unit.