Connecting Controlled Utility Services 

The RLA Controller is not provided with electrical solenoids, contactors, or relays.  

ISIMET

 provides a 

full line of Companion Enclosures and fittings.  It is recommended that these items be included in the 
system design, but when the installer elects to provide these fittings from other sources, compliance with 
product specifications must be confirmed prior to installation. Connect wiring for these devices to 
Terminal 2 at designated posts.  

 
NOTE

:  Place relays and solenoids in areas that are easily accessible for future maintenance. 

 

 

          Touch Panel Switch to Terminal 2 Configuration: (typical) 
    Typical Usage                          Operated By                       Standard Application

 

Terminal 

2

 

Water - Supply 

Leak, Freeze & Seismic Sensor 

Circuit 1 

Post  1 

Water - Supply 

Leak, Freeze & Seismic Sensor 

Circuit 1 

Post  2 

Water - Drain Down 

Freeze & Seismic Sensor 

Circuit 2 

Post  3 

Water - Drain Down 

Freeze & Seismic Sensor 

Circuit 2 

Post  4 

Gas - Supply 

Seismic Sensor 

Circuit 3 

Post  5 

Gas - Supply 

Seismic Sensor 

Circuit 3 

Post  6 

Electrical Shunt 

Seismic Sensor 

Circuit 4 

Post  7 

Electrical Shunt 

Seismic Sensor 

Circuit 4 

Post 8 

 
NOTE:

 Use of primary outputs may be changed to accommodate specific project requirements.   

 
Water Solenoids used with the RLA Controller should be 

ISIMET

 S-220 Series General Service Brass 

Valves with 12-vdc coils. These coils are polarized and must be connected correctly to the Output 
Terminal in order to function as intended. 
Connect Supply Solenoid to the ‘ON w/Latch Terminals.  
Make connections to ‘BLK’ and ‘WHT’ pins to match instructions provided with the solenoids that are 
similarly color coded. Piping and wiring for solenoids should follow details provided with the solenoids. 
  
Gas Solenoids used with the RLA Controller should be 

ISIMET 

S-300 Series Gas Service Valves with 

12-vdc coils. These coils are polarized and must be connected correctly to the Output Terminal in order 
to function as intended. 
Connect Supply Solenoid to the ‘ON w/Latch Terminals.  
Make connections to ‘BLK’ and ‘WHT’ pins to match instructions provided with the solenoids that are 
similarly color coded.  
Piping and wiring for solenoids should follow details provided with the solenoids. 
  
If optional shunt electrical is utilized, make connections at output circuit terminal on 7 and 8.  Must use 
single pole relay with N/O and N/C contacts to shunt electrical. 
 

NOTE:

 Internet connection with remote access available. Refer to User’s Guide

 

 

 

 

 

 

BATTERY BACK UP CONNECTION: (Recommended) 

This unit has been shipped with the battery disconnected to 
prevent discharge during shipment.  Connect the RED 
battery backup wire to the positive (+) terminal, and the 
BLACK backup wire to the negative (-) terminal.  If power 
is lost for an extended period, it is normal for the battery to 
need recharging.  This is done by the ISIMET system, but as 
the battery is a sealed type, it MUST be trickle-charged.  
This charging may take as long as eight hours.  The system 
may be used as normal during this time. 

Содержание RLA Series

Страница 1: ...3 Residential Water Leak Detection RLA 3 Installation Maintenance Operations and Start up Instructions Read all instructions BEFORE installation and USE of Controller KEEP INSTRUCTIONS FOR FUTURE USE...

Страница 2: ...d monitoring systems The system should be thoroughly tested and adjustments made at time of initial operation Periodic testing should be conducted by the user to assure that all components function an...

Страница 3: ...nnecting Controlled Services 10 Battery Backup 10 Connecting Alarm Monitoring Wiring 11 Start Up Checklist 11 Start Up Test Preliminary Information 11 Start Up Test 12 Equipment Operation 13 Troublesh...

Страница 4: ...be confirmed prior to installation Enclosed with this Manual is a separate registration form The front of the form is for equipment warranty registration The back is a copy of the equipment start up c...

Страница 5: ...Page 5...

Страница 6: ...n time to ensure that this occurs A Flush Mounting Trim Flange is provided with each flush mounted unit Separate installation instructions and hardware are included with this flange Semi and Flush Tri...

Страница 7: ...e followed when connecting the conduit to the service panel Figure 4 Controller Knock out holes Wiring the RLA Controller Important Verify that the electrical supply is disconnected prior to connectin...

Страница 8: ...extend lock position STEP 4 Installing Flush Door Trim Figure 7 Prior to installing Door Trim ensure that wall finishes are complete and that the door panel has been installed To install the Flush Doo...

Страница 9: ...escription of Status When Light is On PWR PLC has 24VDC from Power Supply RUN PLC is set to RUN Mode and is operational ERR PLC Processor has incurred an error X1 Door Panic Button is being pressed X2...

Страница 10: ...ctly to the Output Terminal in order to function as intended Connect Supply Solenoid to the ON w Latch Terminals Make connections to BLK and WHT pins to match instructions provided with the solenoids...

Страница 11: ...ct short or input voltage at the output circuit will cause damage to the PLC and Controller Verify that the Door Panel plug is firmly secured to its terminal and ground wire is connected Examine Door...

Страница 12: ...ing system a Press and release the red Panic Button b Verify that all Solenoids have been deactivated 2 Press the Reset System button on the screen NOTE Electrical Service will not shut down with Pani...

Страница 13: ...l breakage in piping or circuits may cause damage to the facility Integral time delay programming insures that brief seismic or similar activity will not affect services To Activate One or More of the...

Страница 14: ...l In many cases failure of the system is the result of improper connection of a remote service or device such as a remote relay solenoid or building alarm system Refer to Equipment Specifications to c...

Страница 15: ...all moisture is removed from the compartment The electronic controller PLC is sensitive to moisture dust debris and other air borne particles Do not expose the interior compartment of the enclosure Du...

Страница 16: ...not specifically intended for use in applications where a master shut down and re instate device is located away from areas of normal use ISIMET s opinion is that in such cases there is risk that the...