2. SPECIFICATIONS
Ethernet:
RS-485:
USB:
3. OPERATING CONDITIONS
4. MOUNTING AND CONNECTION
4.1. Connectors and controls.
ETHERNET
12V
Interface: .......................................................................RJ45 (10/100BASE-T).
Compatibility: ................................................................Ethernet II, IEEE 802.3.
Supported network protocols: .... IP, ARP, TCP, Telnet, ICMP, UDP, DHCP, HTTP.
Maximum line distance: ...........................................................................100 m.
Lines present: .................................................................................................2.
Galvanic isolation: ................................................Line 1 1,000 V, Line 2 none.
Receiver input impedance: .......................................................1/8 of a unit load.
Maximum Line Distance: ......................................................................1,200 m.
Baud rate: .................................................................................
≤
115,200 baud.
Connector: ................................................................................USB 2.0 Type B.
Mode: ........................................................................Full speed, Mass storage.
Max. connection line length: .....................................................................1.8 m.
Power voltage: .........................................................8
…
18 V DC or 7
…
14 V AC.
Consumption current (at 12 V DC): ................................................max. 100 mA.
Dimensions, mm: ............................................................................98 x 67 x 27.
Weight: max. ............................................................................................100 g.
Ambient temperature: 5
…
40°C
Humidity:
≤
80% at 25°C.
When operating under non-recommended conditions, device specifications can deviate from
normal values.
Device must be operated in absence of: precipitation, direct sunlight, sand, dust, and moisture
condensation.
RJ45 connector to join LANs. Requires a standard straight Ethernet patch cable.
power socket. The supplied power adapter gets connected to this socket. If an alternative
power adapter is to be used, it must provide:
- Current: .....................................100 mA and higher;
- Voltage: ........................8
…
18 V DC or 7
…
14 V AC.