Recycle Test Mode = OFF, ON (This is for testing purposes. If selected, it
will cause the gate to cycle open and close unless stopped with the radio
input or turned off in this menu)
Exit the sub-menu
Maintenance Menu
•
Main Power/Battery =
24 VDC
or 12 VDC
(should be set at 24VDC for IQ
Gate operators
•
Maintenance Request in = Cycles or Days
•
Maintenance Request after = _ _ Cycles or _ _ Days
•
Current _ _ _ _ _ _ Cycles/Days – Enter to reset (pressing the
programming knob to enter will erase and reset the current maintenance
count)
•
Total Operator Cycle = M1 00,000,000 (this is displaying the total
accumulated cycles and is non-resetable)
•
Low Power Function =
Hold Open – the gate will hold open until battery is above 75% full
Normal – the gate will continue to function regardless of low power
Fire – the gate will only open from a FIRE input
•
Alarm Relay = Pulsed or Continuous output
•
Motion Warning Type =
3 Sec Pre-Warn – Activates the alarm relay for 3 seconds before
motion
Motion Warning – Activates the alarm relay 3 seconds before
motion as well as during gate motion
Off – no audible notification of gate motion
•
Reset Password = None or New (press enter to setup a new password)
•
Limit Secure = Off or On (this is fail-secure option recommended for use in
the IQ-5000 only)
•
Input Contacts = Momentary or Constant (affects the OPEN and CLOSE
inputs) should be set on Momentary
•
Stop Input = Normally Open(default) or Normally Closed
•
De-Icing Mode
= On or Off (
see below
)
•
Activate De-Icing at Temp: 37 F = (user selectable temperature) this
temperature setting is used to activate the De-Icing mode if activated. It
can also be used to energize the output relays if they have been selected
to activate on a temperature selection
•
Abrupt Reverse =
Off
or On (this selects rather the gate ramps down or
instantly reverses upon a input when closing) Should be set to
OFF
•
Motor Diagnostics View for M1 = Off or On (turns off or on the M1
diagnostics) (
see below
)
•
Motor Diagnostics View for M2 = Off or On
•
Temperature Cal Display = (allows the thermostat to be calibrated
accurately)
Exit the sub-menu
20