Configuration of output1:
Four switching functions are possible:
SP.HY
switch-point / hysteresis
SP.rP
switch-point / release position
FE.HY
window function / hysteresis
FE. rP
window function
/ release position
oFF.1
output 1 „off“
noc 1
noc 1
is only active if in
Ou 1
a switching function is set.
Function of switching output S1:
no.1
(normally open)
nc.1
(normally closed)
ds 1
ds 1
is only active if in
Ou 1
a switching function is set.
on-delay timer function S1
dr 1
ds 1
is only active if in
Ou 1
a switching function is set.
off-delay timer function S1
Ou 2
Configuration output 2:
Four switching functions, the error signal or 4 analog functions
are possible:
SP.HY
switch-point / hysteresis
SP.rP
switch-point / release position
FE.HY
window function / hysteresis
FE. rP
window function
/ release position
Err. 2
error signal
4-20
analog signal 4…20mA
0-20
analog
signal 0…20mA
20-4
analog signal 20…4mA
20-0
analog signal 20…4mA
oFF.2
output 2 „off“
ASP
ASP
is only active if in
Ou 2
an analog signal was set.
Analog starting point:
The pressure value (low pressure) where the analog output
starts.
AEP
AEP
is only active if in
Ou 2
an analog signal was set.
Analog end point:
The pressure value (higher pressure), where the analog signal
ends.
Note:
The minimum range between starting point and end point
is 20% of the measuring range for the DW34 type.