tESt 

Press Enter/Set button for 5sec, then test-function (no timeout) 
With  the  Test-function  you  can  check  the  adjusted  parameters 
without influence for the system. 
The display starts with indicating the current pressure.  
Due  to  the  arrow  keys  the  displayed  value  can  be  increased  or 
decreased.  All  parameters  react  as  if  the  real  pressure  would 
increase or decrease. 
Leave the Test Mode with ESC. 

END 

End of enhanced functions. 
Press  the  Enter/Set  button  twice  to  get  into  the  RUN  mode 
again. 

The units come with an optical interface that allows all parameters to be set and ad-
justed by a PC or notebook. 
The  suitable  interface  cable  and  Windows-Software  can  be  ordered  with  the  article 
number AD000011. 
With the Software you are able to adjust all functions described above. 

NOTE:

 

Use a shielded cable socket (e.g. VK205321), in order to avoid interfer-
ences. 

mounting and electrical connection 

Before mounting and removing the unit: Make sure that no pressure is applied to the 
system. 
Mount the pressure sensor DW34 on a G1/2 – process connection. 
After mounting the sensor mechanically, the control panel can be rotated by 350°. 
Do not touch the opening of the pressure connection with finger or a sharp object. 
This causes irreparable damage to the mebrane! 

The unit must be connected by a suitably qualified electrician. The national and in-
ternational regulations for the installation of electrical equipment must be observed. 
Voltage supply to EN50178. 
Disconnect power before connecting the unit as follows: 

bn=brown, wh=white, bk=black, bl=blue 
terminal marking of the cable socket in brackets 

Содержание DW34311 Series

Страница 1: ...sensor page 1 ipf electronic gmbh Kalver Str 25 27 www ipf electronic com Subject to alteration 58515 L denscheid Germany Tel 49 2351 9365 0 Fax 49 2351 9365 19 info ipf electronic com manual pressure...

Страница 2: ...of the operating elements page 5 menu overview page 6 operation modes of the switching outputs page 8 switch point with release position page 9 switch point with hysteresis page 9 window function with...

Страница 3: ...is siutable for your application without any restrictions Non adherence to the operating instructions or technical data can lead to personal injury and or damage to property In all applications check...

Страница 4: ...e of output 1 lights if the output is switched 3 LED red S2 displays the switching state of output 2 lights if the output is switched 4 programming button Enter Set selection of menus and parameters s...

Страница 5: ...g in PROGRAMM mode saving current value after pressing Enter Set button The indication on the display depends on the programmed function If one of these functions is selected in the enhanced Menu the...

Страница 6: ...s and submenus please press the ESC button again and again until you are back in the RUN mode key lock If the device is in the RUN Mode and you press the arrow keys at the same time for at least 5 sec...

Страница 7: ...n hysteresis output 1 off switching mode S1 switch on delay S1 switch off delay S1 output 2 configuration output 2 S2 output 2 error signal output 2 analog output 2 off switching mode S2 switch on del...

Страница 8: ...tching function normally open no If the switching output 1 is set normally closed nc the states are reversed The minimum range between the switching outputs SP 1 and rSP 1 is 1 of the nominal pressure...

Страница 9: ...ing state changes with the pressure value at rP 1 e g 40bar If SP 1 will be changed rP 1 remains the same The minimum range between SP1 and rSP 1 is 1 of the maximum pressure switch point with hystere...

Страница 10: ...sen switching function no or nc The switching state changes if the pressure leaves the adjusted pressure range The values for the switch point and the release position have to be defined separately If...

Страница 11: ...value Pressing the arrow key downwards or upwards briefly changes the parameter value step by step Pressing the arrow key continuous changes the value fast Pressing the Enter Set button safes the adju...

Страница 12: ...t Enter Set 1X SP1 Press the Enter Set button briefly to get into the main menu Press the Enter Set button again The current value for switch point S1 will be displayed Set the parameter value with th...

Страница 13: ...s 1 is only active if in Ou 1 a switching function is set off delay timer function S1 Ou 2 Configuration output 2 Four switching functions the error signal or 4 analog functions are possible SP HY swi...

Страница 14: ...only noc 2 noc 2 is active if in Ou 2 a switching function is set Function of switching output S2 no 2 normally open nc 2 normally closed dS 2 ds 2 is only active if in Ou 2 a switching function is se...

Страница 15: ...or notebook The suitable interface cable and Windows Software can be ordered with the article number AD000011 With the Software you are able to adjust all functions described above NOTE Use a shielded...

Страница 16: ...pressure is lower than the measuring range SC1 short circuit S1 analog output error signal check wiring check load of S1 SC2 short circuit S2 analog output error signal check wiring check load of S2...

Страница 17: ...splay damping operating temperature temperature drift conn to pressure system sensor head material housing material system of protection electrical connection see list of articles 150 of nominal press...

Страница 18: ...A M12 conn4pin 1 DW343114 34 G1 2A 100bar stainless steel polyester V4A 12 32V DC pnp no nc 0 4 20mA 2x1A M12 conn4pin 1 DW34311G 34 G1 2A 200bar stainless steel polyester V4A 12 32V DC pnp no nc 0 4...

Отзывы: