RBU100H operation manual
3 Product overview
-7-
Designation key
Instruction
E
Power code; 055 means 55kW
F
4: AC 3PH 380V(-15%)
–440V(+10%)
6: AC 3PH 520V(-15%)
–690V(+10%)
3.3 Rated specifications
The rated power of RBU100H is the motor power at 100% braking torque.
3.3.1 380V
Model
Rated
power
(kW)
Rated
current at
DC side (A)
Rated
current at
AC side (A)
Input
reactor
Regenerative
output
reactor
RBU100H-022-4
22
37
30
ACL2-022-4
ERL-022-4-C
RBU100H-030-4
30
51
40
ACL2-030-4
ERL-037-4
RBU100H-045-4
45
77
60
ACL2-045-4
ERL-055-4
RBU100H-055-4
55
96
75
ACL2-055-4
ERL-055-4
RBU100H-090-4
90
150
120
ACL2-075-4
ERL-090-4
RBU100H-110-4
110
183
145
ACL2-1
1
0-4
ERL-090-4
RBU100H-132-4
132
220
176
ACL2-1
60
-4
ERL-132-4
RBU100H-160-4
160
267
213
ACL2-160-4
ERL-160-4-C
RBU100H-200-4
200
333
266
ACL2-2
0
0-4
ERL-220-4
RBU100H-250-4
250
417
330
ACL2-2
8
0-4
ERL-250-4
3.3.2 660V
Model
Rated
power
(kW)
Rated
current at
DC side(A)
Rated
current at
AC side(A)
Input
reactor
Regenerative
output
reactor
RBU100H-055-6
55
52
42
ACL-055-6
ERL-055-6
RBU100H-090-6
90
86
68
ACL-110-6-A
ERL-090-6-A
RBU100H-160-6
160
152
122
ACL-160-6
ERL-160-6
RBU100H-200-6
200
190
152
ACL-200-6
ERL-200-6
RBU100H-315-6
315
300
230
ACL-315-6
ERL-315-6
RBU100H-400-6
400
400
330
ACL-400-6
ERL-400-6
Note:
RBU 380V 22kW
–45 kW has internal output reactor. RBU 380V 55kW–250kW/660V
55kW
–400kW has standard output reactor.
Each RBU100H has 1 standard input reactor. Select the input reactor according to the rated
parameters of the VFD.
The input filter is optional. Select the input filter according to the rated parameters of the VFD.
The fuse is optional. Configure the fuse at 1.5 times of the rated current of the RBU.