4 Installation guidelines
-9-
Environment
Conditions
Storage
temperature
-30
–+60°C
Running
environment
condition
The installation site should:
keep away from the electromagnetic radiation source;
keep away from contaminative air, such as corrosive gas, oil mist
and flammable gas;
ensure foreign objects, such as metal power, dust, oil, water cannot
enter into the RBU(do not install the RBU on the flammable
materials such as wood);
keep away from direct sunlight, oil mist, steam and vibration
environment.
Altitude
Below 1000m
If the sea level is above 1000m, please derate 1% for every
additional 100m.
100%
80%
60%
40%
1000
2000
3000
4000
(
m
)
Iout
Vibration
≤ 5.8m/s
2
(0.6g)
Installation direction
The RBU should be installed on an upright position to ensure
sufficient cooling effect.
Note:
RBU100H should be installed in a clean and ventilated environment according to enclosure
classification.
Cooling air must be clean, free from corrosive materials and electrically conductive dust.
4.2 Installation direction
The RBU100H may be installed on the wall or in a cabinet.
The RBU100H must be installed in an upright position. Check the installation site according to the
requirements below.
Refer to chapter 9 Dimension and size for frame details.
4.3 Installation steps
(1) Mark the hole location. The location of the holes is shown in the dimension drawings in chapter 9