RBU100H operation manual
6 Function parameters
-18-
6 Function parameters
6.1 Function code
Code
Name
Detailed instruction
Default
Modify
P0.00
Control mode
0
–1
0: Keypad
1: Terminal
S1 valid: automatic operation
S2 valid: manual operation
1
◎
P0.01
Keypad control
0
–1
0: Automatic operation
1: Manual operation
0
◎
P0.02
Filter time
1
–10
1
◎
P0.03
DC bus voltage
establishment time
0
–10000ms
10000ms
○
P0.04
Regenerative voltage
difference during
starting
0.0
–240.0V
380V voltage degree
660V voltage degree
40.0V
60.0V
○
P0.05
Regenerative voltage
difference during
stopping
0.0
–120.0V
380V voltage degree
660V voltage degree
10.0V
15.0V
○
P0.06
Regenerative stop
time
0.1
–10.0s
1.0s
○
P0.07
Input frequency
0~1
0:50Hz
1:60Hz
0
◎
P0.08
S3 function
1
–15
3:Valid when connect S3 to COM
Other reserved
3 (external
fault)
◎
P0.09
S4 function
1
–15
2: Valid when connect S4 to COM
Other reserved
2 (fault
reset)
◎
P0.10
Reserved
1
○
P0.11
AO output
0
–8
0: DC
voltage(0
–1000V/1500V/3000V)
1: Output current (0
–200.0%)
2
–8: Reserved
1
○
P0.12
Lower limit of AO
output
0.0%
–100.0%
0.0%
○