RBU100H

 

 

Regenerative Energy Unit

Содержание RBU100H

Страница 1: ...RBU100H Regenerative Energy Unit...

Страница 2: ...ions 7 4 Installation guidelines 8 4 1 Installation environment 8 4 2 Installation direction 9 4 3 Installation steps 9 4 4 Terminals and function 11 4 5 Standard wiring 12 4 6 Parallel connection 13...

Страница 3: ...emergency 1 2 Warning symbols Warnings caution you about conditions which can result in serious injury or death damage to the equipment and advice on how to avoid the danger Following warning symbols...

Страница 4: ...proper environment Avoid any conductive objects on the front cover otherwise electrical shock may occur Tighten up the screws when wiring otherwise fire leakage current may occur 1 3 2 Commissioning...

Страница 5: ...nd replacement of components Only qualified electricians are allowed to perform the maintenance inspection and components replacement of the RBU Disconnect all power supplies to the RBU before the ter...

Страница 6: ...the ambient temperature of the RBU is below 40 C If exceeds derate 3 for every additional 1 C Additionally the RBU cannot be used if the ambient temperature is above 50 C 2 Check that the ambient tem...

Страница 7: ...ement 5 Check that all grounding systems are properly grounded according to the requirements of the RBU 6 Check that the free space during installation is sufficient according to the instructions in u...

Страница 8: ...er than 0 9 Overload capacity 60s with 150 of rated current Operation mode External terminal Keyboard Fault output Relay output Status display LED keypad Analog output Voltage 0 10V Overcurrent protec...

Страница 9: ...60 4 ERL 160 4 C RBU100H 200 4 200 333 266 ACL2 200 4 ERL 220 4 RBU100H 250 4 250 417 330 ACL2 280 4 ERL 250 4 3 3 2 660V Model Rated power kW Rated current at DC side A Rated current at AC side A Inp...

Страница 10: ...beyond the assured maintenance range may occur Don not hold the front cover only during moving otherwise the machine may fall 4 1 Installation environment The installation environment is the safeguar...

Страница 11: ...very additional 100m 100 80 60 40 1000 2000 3000 4000 m Iout Vibration 5 8m s2 0 6g Installation direction The RBU should be installed on an upright position to ensure sufficient cooling effect Note R...

Страница 12: ...n the drive onto the wall 4 Tighten the screws in the wall securely Figure 4 1 Installation space Note The minimum space of B and C is 100mm Multiple vertical installation Figure 4 2 UP DOWN installat...

Страница 13: ...to RBU and fire may occur The r s and t of the RBU connect to 3PH power terminals R S and T respectively see Figure 4 5 and Figure 4 6 Otherwise breaker tripping or RBU fault or even damage may occur...

Страница 14: ...RO1B RO1C RO1 relay output ROA common terminal ROB NC ROC NO Contactor capability AC250V 3A DC30V 1A 4 5 Standard wiring 4 5 1 400V 22kW 45kW R S T U V W R S T r s t S1 S2 S3 S4 COM 24V Y COM M Power...

Страница 15: ...generative system RBU Port of external keypad Open collector output RO Figure 4 6 Standard wiring of RBU 380V 55kW 250kW 660V 55kW 400kW Note RBU 380V 55kW 250kW 660V 55kW 400kW has standard input out...

Страница 16: ...Connection instruction make the first RBU as the master and others as the slave in parallel connection Connect the Y and COM terminal of the first RBU to the S2 and COM terminal of the second one thi...

Страница 17: ...tive reactor It is recommended to use fuse RBU RBU Figure 4 8 Parallel connection 2 of RBU100H Note RBU100H 380V 22kW 45kW has internal output reactor RBU100H 380V 55kW 250kW 660V 55kW 400kW has stand...

Страница 18: ...m 5 1 2 Buttons Button Name Function PRG ESC Program Key Enter or escape from the first level menu to delete the parameter quickly DATA ENT Enter Key Progressively enter menu and confirm parameters UP...

Страница 19: ...s Flickering parameter autotuning status Light on operating status LOCAL REMOT Extinguished keypad control Flickering terminal control Light on communication control TRIP Extinguished normal operation...

Страница 20: ...ifference during starting 0 0 240 0V 380V voltage degree 660V voltage degree 40 0V 60 0V P0 05 Regenerative voltage difference during stopping 0 0 120 0V 380V voltage degree 660V voltage degree 10 0V...

Страница 21: ...of the heat sink exceeds 45 C 1 P0 17 Y switch output selection 0 15 0 No output 1 Operation command valid 2 Regenarative output 3 Reserved 4 Fault output 5 15 Reserved 0 P0 18 RO selection 4 fault ou...

Страница 22: ...6 OC3 7 Reserved 8 Reserved 9 OV3 10 UV 11 Reserved 12 OL2 13 Reserved 14 SPO 15 Reserved 16 OH2 17 EF 18 Reserved 19 ItE 20 Reserved 21 EEP 22 Reserved 23 Reserved 24 Reserved 25 CP 26 PEr P0 28 Prev...

Страница 23: ...peration 0 Automatic operation In automatic operation the RBU detects the DC voltage and the operation stops The RBU works when DC voltage of the VFD standard DC voltage P0 04 The RBU stops when DC vo...

Страница 24: ...nput power 2 Select the RBU with a larger power 3 Ask for help OV3 Over voltage in running 1 The input voltage is abnormal 2 There is large energy feedback 1 Check the input power 2 Check if the DEC t...

Страница 25: ...ault S3 external fault input terminals action 1 Check the external device input 2 Ask for help ItE Current detection fault The connection of the control board is not good 1 Check the connector and rec...

Страница 26: ...main circuit and control circuit are normal Measurement by millimeter Conforming to the manual Main circuit For public use Ensure the screws are tightened up Tighten up NA Ensure there is no distorti...

Страница 27: ...Ensure there is no smelling and color changing Smelling and visual examination NA Ensure there are no crackles damage distortion and rust Visual examination NA Ensure there is no weeping and distorti...

Страница 28: ...mptoms appear Replacement fans are available from INVT 8 2 1 Replacing the cooling fan Read and follow the instructions in chapter 1 Safety precautions Ignoring the instructions would cause physical i...

Страница 29: ...with single three phase 220V AC as its input voltage The RBU with single three phase 220V AC as its input voltage can apply Single phase 220V AC 2A power surge All DC bus capacitors charge at the sam...

Страница 30: ...electrolytic capacitors in the RBU are above 35000 Please contact with the local INVT offices or dial our national service hotline 400 700 9997 for detailed operation 8 4 Power cables Read and follow...

Страница 31: ...RBU100H operation manual 9 Dimension and size 29 9 Dimension and size 9 1 Dimension of the keypad Figure 9 1 Dimension of the external keypad big Figure 9 2 Hole dimension of the external keypad big...

Страница 32: ...nstallation hole mm Recommended screw Gross weight kg Installation dimension External dimension 380V 22 45kW 130 140 563 5 220 577 236 7 M6 16 41 55 132kW 130 140 563 5 320 577 261 7 M6 16 32 160 250k...