Goodrive300-LIFT series inverter
Function parameters
-67-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P14.01
Communication
baud ratio
Sets the digital transmission speed between the
upper monitor and the inverter.
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
7: 115200BPS
Note
: The baud rate between the upper PC and
the inverter must be the same. Otherwise, the
communication is not applied. The bigger the
baud rate, the quicker the communication
speed.
4
○
P14.02 Digital bit check
The data format between the upper monitor and
the inverter must be the same. Otherwise, the
communication fails.
0: No check (N,8,1) for RTU
1: Even check (E,8,1) for RTU
2: Odd check (O,8,1) for RTU
3: No check (N,8,2) for RTU
4: Even check (E,8,2) for RTU
5: Odd check(O,8,2) for RTU
1
○
P14.03
Answer delay
0
–
200ms
The interval time when the drive receives the
data and sent it to the upper monitor. If the
answer delay is shorter than the system
processing time, then the answer delay time is
the system processing time, if the answer delay
is longer than the system processing time, then
after the system deal with the data, waits until
achieving the answer delay time to send the
data to the upper monitor.
5
○