When using the off grid function, please add off grid AC breaker in off grid output
cable to ensure safety.
BD6KTL-
RH1
BD7K6TL-
RH1
BD9KTL-
RH1
BD10KTL-
RH1
BD11K4TL-
RH1
Micro-breake
r
32A
40A
50A
64A
64A
Note:
The absence of AC breaker on back-up side will lead to inverter damage if an
electrical short circuit happens on back-up side.
Step1
. Make BACK-UP wires like Grid wires.
BD6KTL-
RH1
BD7K6TL-
RH1
BD9KTL-
RH1
BD10KTL-
RH1
BD11K4TL-
RH1
Cable
10AWG
8AWG
8AWG
7AWG
7AWG
Requirements for BACK-UP load
WARNING!
Make sure the BACK-UP load power rating is within BACK-UP output rating, otherwise the
inverter will shutdown with an “over load” warning.
When an “over load” is appeared, adjust the load power to make sure it is within the
BACK-UP output power range, then turn the inverter back on.
For the nonlinear load, please make sure the inrush power should be within the BACK-UP
output power range.
5.4 Battery Connection
Charging & discharging system of inverter is designed for high-voltage lithium battery.
Before choosing battery, please note the maximum voltage of battery cannot exceed 350V
and the rated voltage of battery cannot exceed 336V, and the battery communication should
be compatible with inverter.
Battery breaker
Before connecting to battery, please install a nonpolar DC breaker to make sure inverter can
be securely disconnected during maintenance.
Model
BD6KTL-RH1 BD7K6TL-RH1 BD9KTL-RH1 BD10KTL-RH1 BD11K4TL-RH1
Voltage
Nominal voltage of DC breaker should be larger than maximum voltage of
battery
Current(A)
110A