background image

Optidrive ODE-2 User Guide Revision 3.30 

 

www.invertekdrives.com 

13

 

 

4

 
Pow

er

 W

iri

n

4.3.

 

Incoming Power Connection 

 

For 1 phase supply, power should be connected to L1/L, L2/N. 

 

For 3 phase supplies, power should be connected to L1, L2, and L3.  Phase sequence is not important. 

 

For compliance with CE and C Tick EMC requirements, a symmetrical shielded cable is recommended. 

 

A fixed installation is required according to IEC61800-5-1 with a suitable disconnecting device installed between the Optidrive and the 
AC Power Source. The disconnecting device must conform to the local safety code / regulations (e.g. within Europe, EN60204-1, Safety 
of machinery).  

 

The cables should be dimensioned according to any local codes or regulations. Guideline dimensions are given in section 9.2. 

 

Suitable fuses to provide wiring protection of the input power cable should be installed in the incoming supply line, according to the 
data in section 9.2. The fuses must comply with any local codes or regulations in place.  In general, type gG (IEC 60269) or UL type T 
fuses are suitable; however in some cases type aR fuses may be required. The operating time of the fuses must be below 0.5 seconds. 

 

Where allowed by local regulations, suitably dimensioned type B MCB circuit breakers of equivalent rating may be utilised in place of 
fuses, providing that the clearing capacity is sufficient for the installation.  

 

When the power supply is removed from the drive, a minimum of 30 seconds should be allowed before re-applying the power. A 
minimum of 5 minutes should be allowed before removing the terminal covers or connection. 

 

The maximum permissible short circuit current at the Optidrive Power terminals as defined in IEC60439-1 is 100kA. 

 

An optional Input Choke is recommended to be installed in the supply line for drives where any of the following conditions occur:- 

o

 

The incoming supply impedance is low or the fault level / short circuit current is high 

o

 

The supply is prone to dips or brown outs 

o

 

An imbalance exists on the supply (3 phase drives) 

o

 

The power supply to the drive is via a busbar and brush gear system (typically overhead Cranes). 

 

In all other installations, an input choke is recommended to ensure protection of the drive against power supply faults. Part numbers 
are shown in the table. 

Supply 

Frame Size 

AC Input Inductor 

230 Volt 

1 Phase 

OPT-2-L1016-20 

OPT-2-L1025-20 

N/A 

400 Volt 

3 Phase 

OPT-2-L3006-20 

OPT-2-L3010-20 

OPT-2-L3036-20 

4.4.

 

Drive and Motor Connection 

 

The drive inherently produces fast switching of the output voltage (PWM) to the motor compared to the mains supply, for motors 
which have been wound for operation with a variable speed drive then there is no preventative measures required, however if the 
quality of insulation is unknown then the motor manufacturer should be consulted and preventative measures may be required. 

 

The motor should be connected to the Optidrive U, V, and W terminals using a suitable 3 or 4 core cable. Where a 3 core cable is 
utilised, with the shield operating as an earth conductor, the shield must have a cross sectional area at least equal to the phase 
conductors when they are made from the same material. Where a 4 core cable is utilised, the earth conductor must be of at least 
equal cross sectional area and manufactured from the same material as the phase conductors. 

 

The motor earth must be connected to one of the Optidrive earth terminals. 

 

For compliance with the European EMC directive, a suitable screened (shielded) cable should be used. Braided or twisted type 
screened cable where the screen covers at least 85% of the cable surface area, designed with low impedance to HF signals are 
recommended as a minimum. Installation within a suitable steel or copper tube is generally also acceptable. 

 

The cable screen should be terminated at the motor end using an EMC type gland allowing connection to the motor body through the 
largest possible surface area 

 

Where drives are mounted in a steel control panel enclosure, the cable screen may be terminated directly to the control panel using a 
suitable EMC clamp or gland, as close to the drive as possible. 

 

For IP66 drives, connect the motor cable screen to the internal ground clamp 

4.5.

 

Motor Terminal Box Connections 

Most general purpose motors are wound for operation on dual voltage supplies. This is indicated on the nameplate of the motor. This 
operational voltage is normally selected when installing the motor by selecting either STAR or DELTA connection.  STAR always gives the higher 
of the two voltage ratings. 

Incoming Supply Voltage 

Motor Nameplate Voltages 

Connection 

230 

230 / 400 

Delta 

 

400 

400 / 690 

400 

230 / 400 

Star 

 

Содержание Optidrive ODE-2-11005-1H01

Страница 1: ...ptidrive ODE 2 User Guide Revision 3 30 www invertekdrives com 1 1 Introduction User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 11kW 0 5 15HP 110 480V Installation and Operating Instructions...

Страница 2: ...13 Motor Nameplate Details Enter the motor rated voltage in P 07 Enter the motor rated current in P 08 Enter the motor rated frequency in P 09 Keypad operation can be found on page 16 Control Termina...

Страница 3: ...nter the motor rated current in P 08 Enter the motor rated frequency in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse...

Страница 4: ...cy in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse Ratings given on page 26 Recommended cable sizes shown on page 26...

Страница 5: ...factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted For shielded motor cable lengths greater than 100m and...

Страница 6: ...ctions 13 4 6 Motor Thermal overload Protection 14 4 7 Control Terminal Wiring 14 4 8 Connection Diagram 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4 10 Control Terminal Conne...

Страница 7: ...es or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the drive control cables whilst power i...

Страница 8: ...50 1KB4 ODE 2 22150 1K04 1 5 ODE 2 22020 1HB4 ODE 2 22020 1H04 2 7 2 ODE 2 22220 1KB4 ODE 2 22220 1K04 2 2 ODE 2 22030 1HB4 ODE 2 22030 1H04 3 10 5 2 N A ODE 2 32040 1K04 2 4 0 N A ODE 2 32050 1H04 2...

Страница 9: ...97 5 5 0 22 10 0 39 1 0 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 110 4 33 63 2 48 5 5 0 22 10 0 39 1 7 3 8 3 261 10 28 246 9 69 247 9 72 6 0 24 175 6 89 131 5 16 80 3 15 5 5 0 22 1...

Страница 10: ...All Frame Sizes Control Terminals 0 5 Nm 4 5 lb in Power Terminals 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmen...

Страница 11: ...For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched mo...

Страница 12: ...tor ground must be connected to one of the ground terminals on the drive Ground Fault Monitoring As with all inverters a leakage current to earth can exist The Optidrive is designed to produce the min...

Страница 13: ...t power supply faults Part numbers are shown in the table Supply Frame Size AC Input Inductor 230 Volt 1 Phase 1 OPT 2 L1016 20 2 OPT 2 L1025 20 3 N A 400 Volt 3 Phase 2 OPT 2 L3006 20 2 OPT 2 L3010 2...

Страница 14: ...of different voltages e g 24 Volt DC and 110 Volt AC should not be routed in the same cable Maximum control terminal tightening torque is 0 5Nm Control Cable entry conductor size 0 05 2 5mm 2 30 12 A...

Страница 15: ...un in PI Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Pres...

Страница 16: ...turned to minimum 5 Turn the potentiometer to maximum The motor will accelerate to 50Hz the default value of P 01 under the control of the accelerating ramp time P 03 The display shows 50Hz at max sp...

Страница 17: ...the motor P 10 Motor Rated Speed 0 30000 0 Rpm This parameter can optionally be set to the rated nameplate rpm of the motor When set to the default value of zero all speed related parameters are displ...

Страница 18: ...1 0 0 Hz Rpm P 21 Preset Frequency Speed 2 P 02 P 01 0 0 Hz Rpm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected...

Страница 19: ...external thermal protection device should be fitted P 35 Analog Input 1 Scaling 0 0 500 0 100 0 Scales the analog input by this factor e g if P 16 is set for a 0 10V signal and the scaling factor is s...

Страница 20: ...erence between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops suffi...

Страница 21: ...tching Frequency 4 to 32 kHz Actual drive effective output switching frequency This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce th...

Страница 22: ...e or similar to digital input 3 7 Open Stop disable Closed Fwd Run enable Open Stop disable Closed Rev Run enable External trip input Open Trip Closed Run Analog input 1 reference Closing digital inpu...

Страница 23: ...ton Open Keypad speed ref 24V Preset speed 1 3 1 Open Stop disable Closed Run enable Closed remote UP push button External trip input Open Trip Closed Run Closed remote DOWN push button Connect extern...

Страница 24: ...trip input Open Trip Closed Run PI feedback analog input Connect external motor thermistor PTC type or similar to digital input 3 4 Normally Open NO Momentary close to run Normally Closed NC Momentary...

Страница 25: ...2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Checksum...

Страница 26: ...75 1 8 5 16 10 1 5 14 4 3 1 5 14 50 N A 1 1 5 2 13 9 25 20 2 5 12 7 1 5 14 50 N A 2 1 5 2 15 2 25 20 2 5 12 7 1 5 14 100 100 2 2 2 3 19 5 25 25 4 10 10 5 1 5 14 100 50 3 4 5 30 5 40 40 4 8 16 2 5 12...

Страница 27: ...recommends the installation of input line reactors Frequency 50 60Hz 5 Variation Short Circuit Capacity Voltage Rating Min kW HP Max kW HP Maximum supply short circuit current 115V 0 37 0 5 1 1 1 5 5...

Страница 28: ...vertek standard braking resistor is being used P 34 MUST be 1 Increase the deceleration time P 04 or 2nd deceleration time P 24 Reduce the load inertia For Other Brake Resistors Ensure the resistance...

Отзывы: