Optidrive ODE-2 User Guide Revision 3.30
24
www.invertekdrives.com
7
A
n
al
og and
Di
gi
ta
l I
n
p
u
t
Co
n
fi
gu
ra
ti
on
s
7.3.
Modbus Control Mode (P-12 = 3 or 4)
P-15 Digital input 1 (T2)
Digital input 2 (T3)
Digital input 3 (T4)
Analog input (T6)
Comments
0, 2,
4..5,
8..12
Open: Stop (disable)
Closed: Run (enable)
No effect
No effect
No effect
Run and stop commands
given via the RS485 link and
Digital input 1 must be closed
for the drive to run.
1
Open: Stop (disable)
Closed: Run (enable)
No effect
No effect
No effect
Speed reference = PI
Controller Output
3
1)
Open: Stop (disable)
Closed: Run (enable)
Open : Master speed ref
Closed : Preset speed 1
External trip input :
Open: Trip, Closed: Run
No effect
Connect external motor
thermistor PTC type or
similar to digital input 3
6
1)
Open: Stop (disable)
Closed: Run (enable)
Open : Master speed ref
Closed : Analog input
External trip input :
Open: Trip, Closed: Run
Analog input reference
Master Speed Ref - start and
stop controlled via RS485.
Keypad Speed Ref - drive
auto runs if digital input 1
closed, depending on P-31
setting
7
1)
Open: Stop (disable)
Closed: Run (enable)
Open : Master speed ref
Closed : keypad speed ref
External trip input :
Open: Trip, Closed: Run
No effect
For further information on the MODBUS RTU Register Map information and communication setup; please contact your Invertek Drives Sales
Partner.
7.4.
User PI Control Mode (P-12 = 5 or 6)
P-15
Digital input 1 (T2)
Digital input 2 (T3)
Digital input 3 (T4)
Analog input (T6)
Comments
0, 2,
9..12
Open: Stop (disable)
Closed: Run (enable)
Open : PI control
Closed : Preset speed 1
PI feedback analog input
Analog input 1
Analog Input 1 can provide
an adjustable PI setpoint, by
setting P-44 = 1
1
Open: Stop (disable)
Closed: Run (enable)
Open : PI control
Closed : Analog input 1
PI feedback analog input
Analog input 1
Analog Input 1 can provide
an adjustable PI setpoint, by
setting P-44 = 1
3, 7
1)
Open: Stop (disable)
Closed: Run (enable)
Open : PI control
Closed : Preset speed 1
External trip input :
Open: Trip, Closed: Run
PI feedback analog input
Connect external motor
thermistor PTC type or
similar to digital input 3
4
Normally Open (NO)
Momentary close to run
Normally Closed (NC)
Momentary open to stop
PI Feedback Analog Input
Analog Input 1
Normally Open (NO)
Momentary close to run
5
Normally Open (NO)
Momentary close to run
Normally Closed (NC)
Momentary open to stop
Open: PI Control
Closed: Preset Speed 1
PI Feedback Analog Input
Normally Open (NO)
Momentary close to run
6
Normally Open (NO)
Momentary close to run
Normally Closed (NC)
Momentary open to stop
Open: External Trip
Closed: Run
PI Feedback Analog Input
Normally Open (NO)
Momentary close to run
8
Open: Stop (disable)
Closed: Run (enable)
Open : Forward run
Closed : Reverse run
PI feedback analog input
Analog input 1
Analog Input 1 can provide
an adjustable PI setpoint, by
setting P-44 = 1
Example Wiring
PI Mode P-12=5, P-15=0
PI Mode P-12=5, P-15=1
PI Mode P-12=5, P-15=3
+24 Volt
+24 Volt
+24 Volt
Run (Enable)
Run (Enable)
Run (Enable)
PI / Preset Speed 1
PI / Local (Hand)
PI / Preset Speed 1
PI Feedback
PI Feedback
External Trip
+10 Volt
Local (Hand) Ref
PI Feedback
0 Volt
0 Volt
0 Volt
Remote closed loop PI feedback control
with Local Preset speed 1
Remote closed loop PI feedback control with
Local Analog speed input
Remote closed loop PI feedback control with
Local Preset speed 1 and motor thermistor
trip
NOTE
By default the PI reference is set for a digital reference level set in P-45.
When using an Analog reference set P-44 = 1 (analog) and connect reference signal to analog input 1 (T6).
The default settings for proportional gain (P-41), integral gain (P-42) and feedback mode (P-43) are suitable for most HVAC and pumping
applications.
The analog reference used for PI controller can also be used as the local speed reference when P15=1.
7.5.
Motor Thermistor Connection
1 : + 24 Volt
The motor thermistor should be connected between terminals 1 and 4 as shown. A
setting of P-15 where Digital Input 3 is programmed for ‘External Trip’ must be used.
The current flow through the thermistor is automatically controlled to prevent a
failure.
4 : External Trip