background image

Optidrive ODE-2 User Guide Revision 3.30 

24 

www.invertekdrives.com 

 

 

7

 

A

n

al

og and

 Di

gi

ta

l I

n

p

u

Co

n

fi

gu

ra

ti

on

7.3.

 

Modbus Control Mode (P-12 = 3 or 4) 

P-15  Digital input 1 (T2) 

Digital input 2 (T3) 

Digital input 3 (T4) 

Analog input (T6) 

Comments 

0, 2, 
4..5, 

8..12 

Open: Stop (disable) 
Closed: Run (enable) 

No effect 

No effect 

No effect 

Run and stop commands 
given via the RS485 link and 
Digital input 1 must be closed 
for the drive to run.  

Open: Stop (disable) 
Closed: Run (enable) 

No effect 

No effect 

No effect 

Speed reference = PI 
Controller Output 

1)

 

Open: Stop (disable) 
Closed: Run (enable) 

Open : Master speed ref 
Closed : Preset speed 1 

External trip input : 
Open: Trip, Closed: Run 

No effect 

Connect external motor 
thermistor PTC type or 
similar to  digital input 3  

1)

 

Open: Stop (disable) 
Closed: Run (enable) 

Open : Master speed ref 
Closed : Analog input 

External trip input : 
Open: Trip, Closed: Run 

Analog input reference 

Master Speed Ref - start and 
stop controlled via RS485. 
Keypad Speed Ref - drive 
auto runs if digital input 1 
closed, depending on P-31 
setting 

1)

 

Open: Stop (disable) 
Closed: Run (enable) 

Open : Master speed ref 
Closed : keypad speed ref 

External trip input : 
Open: Trip, Closed: Run 

No effect 

For further information on the MODBUS RTU Register Map information and communication setup; please contact your Invertek Drives Sales 
Partner. 

7.4.

 

User PI Control Mode (P-12 = 5 or 6) 

P-15 

Digital input 1 (T2) 

Digital input 2 (T3) 

Digital input 3 (T4) 

Analog input (T6) 

Comments 

0, 2, 

9..12 

Open: Stop (disable) 
Closed: Run (enable) 

Open : PI control 
Closed : Preset speed 1 

PI feedback analog input 

Analog input 1 

Analog Input 1 can provide 
an adjustable PI setpoint, by 
setting P-44 = 1 

Open: Stop (disable) 
Closed: Run (enable) 

Open : PI control 
Closed : Analog input 1 

PI feedback analog input 

Analog input 1 

Analog Input 1 can provide 
an adjustable PI setpoint, by 
setting P-44 = 1 

3, 7 

1)

 

Open: Stop (disable) 
Closed: Run (enable) 

Open :  PI control 
Closed : Preset speed 1 

External trip input : 
Open: Trip, Closed: Run 

PI feedback analog input 

Connect external motor 
thermistor PTC type or 
similar to  digital input 3  

Normally Open (NO) 
Momentary close to run 

Normally  Closed (NC) 
Momentary open to stop 

PI Feedback Analog Input 

Analog Input 1 

Normally Open (NO) 
Momentary close to run 

Normally Open (NO) 
Momentary close to run 

Normally  Closed (NC) 
Momentary open to stop 

Open: PI Control 
Closed: Preset Speed 1 

PI Feedback Analog Input 

Normally Open (NO) 
Momentary close to run 

Normally Open (NO) 
Momentary close to run 

Normally  Closed (NC) 
Momentary open to stop 

Open: External Trip 
Closed: Run 

PI Feedback Analog Input 

Normally Open (NO) 
Momentary close to run 

Open: Stop (disable) 
Closed: Run (enable) 

Open : Forward run 
Closed : Reverse run 

PI feedback analog input 

Analog input 1 

Analog Input 1 can provide 
an adjustable PI setpoint, by 
setting P-44 = 1 

 
Example Wiring 

PI Mode P-12=5, P-15=0

 

PI Mode P-12=5, P-15=1

 

PI Mode P-12=5, P-15=3

 

 

+24 Volt 

 

+24 Volt 

 

+24 Volt 

Run (Enable) 

Run (Enable) 

Run (Enable) 

PI / Preset Speed 1 

PI / Local (Hand) 

PI / Preset Speed 1 

PI Feedback 

PI Feedback 

External Trip 

 

+10 Volt 

 

 

Local (Hand) Ref 

PI Feedback 

0 Volt 

0 Volt 

0 Volt 

Remote closed loop PI feedback control 

with Local Preset speed 1

 

Remote closed loop PI feedback control with 

Local Analog speed input

 

Remote closed loop PI feedback control with 

Local Preset speed 1 and motor thermistor 

trip

 

 

NOTE 

By default the PI reference is set for a digital reference level set in P-45. 
When using an Analog reference set P-44 = 1 (analog) and connect reference signal to analog input 1 (T6). 
The default settings for proportional gain (P-41), integral gain (P-42) and feedback mode (P-43) are suitable for most HVAC and pumping 
applications. 
The analog reference used for PI controller can also be used as the local speed reference when P15=1. 

7.5.

 

Motor Thermistor Connection 

 

1 : + 24 Volt 

The motor thermistor should be connected between terminals 1 and 4 as shown. A 
setting of P-15 where Digital Input 3 is programmed for ‘External Trip’ must be used. 
The current flow through the thermistor is automatically controlled to prevent a 
failure. 

4 : External Trip 

 

 

Содержание Optidrive ODE-2-11005-1H01

Страница 1: ...ptidrive ODE 2 User Guide Revision 3 30 www invertekdrives com 1 1 Introduction User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 11kW 0 5 15HP 110 480V Installation and Operating Instructions...

Страница 2: ...13 Motor Nameplate Details Enter the motor rated voltage in P 07 Enter the motor rated current in P 08 Enter the motor rated frequency in P 09 Keypad operation can be found on page 16 Control Termina...

Страница 3: ...nter the motor rated current in P 08 Enter the motor rated frequency in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse...

Страница 4: ...cy in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse Ratings given on page 26 Recommended cable sizes shown on page 26...

Страница 5: ...factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted For shielded motor cable lengths greater than 100m and...

Страница 6: ...ctions 13 4 6 Motor Thermal overload Protection 14 4 7 Control Terminal Wiring 14 4 8 Connection Diagram 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4 10 Control Terminal Conne...

Страница 7: ...es or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the drive control cables whilst power i...

Страница 8: ...50 1KB4 ODE 2 22150 1K04 1 5 ODE 2 22020 1HB4 ODE 2 22020 1H04 2 7 2 ODE 2 22220 1KB4 ODE 2 22220 1K04 2 2 ODE 2 22030 1HB4 ODE 2 22030 1H04 3 10 5 2 N A ODE 2 32040 1K04 2 4 0 N A ODE 2 32050 1H04 2...

Страница 9: ...97 5 5 0 22 10 0 39 1 0 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 110 4 33 63 2 48 5 5 0 22 10 0 39 1 7 3 8 3 261 10 28 246 9 69 247 9 72 6 0 24 175 6 89 131 5 16 80 3 15 5 5 0 22 1...

Страница 10: ...All Frame Sizes Control Terminals 0 5 Nm 4 5 lb in Power Terminals 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmen...

Страница 11: ...For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched mo...

Страница 12: ...tor ground must be connected to one of the ground terminals on the drive Ground Fault Monitoring As with all inverters a leakage current to earth can exist The Optidrive is designed to produce the min...

Страница 13: ...t power supply faults Part numbers are shown in the table Supply Frame Size AC Input Inductor 230 Volt 1 Phase 1 OPT 2 L1016 20 2 OPT 2 L1025 20 3 N A 400 Volt 3 Phase 2 OPT 2 L3006 20 2 OPT 2 L3010 2...

Страница 14: ...of different voltages e g 24 Volt DC and 110 Volt AC should not be routed in the same cable Maximum control terminal tightening torque is 0 5Nm Control Cable entry conductor size 0 05 2 5mm 2 30 12 A...

Страница 15: ...un in PI Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Pres...

Страница 16: ...turned to minimum 5 Turn the potentiometer to maximum The motor will accelerate to 50Hz the default value of P 01 under the control of the accelerating ramp time P 03 The display shows 50Hz at max sp...

Страница 17: ...the motor P 10 Motor Rated Speed 0 30000 0 Rpm This parameter can optionally be set to the rated nameplate rpm of the motor When set to the default value of zero all speed related parameters are displ...

Страница 18: ...1 0 0 Hz Rpm P 21 Preset Frequency Speed 2 P 02 P 01 0 0 Hz Rpm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected...

Страница 19: ...external thermal protection device should be fitted P 35 Analog Input 1 Scaling 0 0 500 0 100 0 Scales the analog input by this factor e g if P 16 is set for a 0 10V signal and the scaling factor is s...

Страница 20: ...erence between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops suffi...

Страница 21: ...tching Frequency 4 to 32 kHz Actual drive effective output switching frequency This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce th...

Страница 22: ...e or similar to digital input 3 7 Open Stop disable Closed Fwd Run enable Open Stop disable Closed Rev Run enable External trip input Open Trip Closed Run Analog input 1 reference Closing digital inpu...

Страница 23: ...ton Open Keypad speed ref 24V Preset speed 1 3 1 Open Stop disable Closed Run enable Closed remote UP push button External trip input Open Trip Closed Run Closed remote DOWN push button Connect extern...

Страница 24: ...trip input Open Trip Closed Run PI feedback analog input Connect external motor thermistor PTC type or similar to digital input 3 4 Normally Open NO Momentary close to run Normally Closed NC Momentary...

Страница 25: ...2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Checksum...

Страница 26: ...75 1 8 5 16 10 1 5 14 4 3 1 5 14 50 N A 1 1 5 2 13 9 25 20 2 5 12 7 1 5 14 50 N A 2 1 5 2 15 2 25 20 2 5 12 7 1 5 14 100 100 2 2 2 3 19 5 25 25 4 10 10 5 1 5 14 100 50 3 4 5 30 5 40 40 4 8 16 2 5 12...

Страница 27: ...recommends the installation of input line reactors Frequency 50 60Hz 5 Variation Short Circuit Capacity Voltage Rating Min kW HP Max kW HP Maximum supply short circuit current 115V 0 37 0 5 1 1 1 5 5...

Страница 28: ...vertek standard braking resistor is being used P 34 MUST be 1 Increase the deceleration time P 04 or 2nd deceleration time P 24 Reduce the load inertia For Other Brake Resistors Ensure the resistance...

Отзывы: