Par
Name
Minimum
Maximum
Default
Units
P8-16
Standby Activation Level
0.0
100.0
0.0
%
Specifies the level for the drive to wake up from a standby condition.
If P8-14 = 1:
When the PID operates in direct mode (P3-04=0), if the level of the PID feedback is lower than this level, the drive will wake up after the
time set up in P8-17 has elapsed. The delay timer will reset to 0 if the feedback goes above this level in the meantime.
When the PID operates in inverse mode (P3-04=1), if the level of the PID feedback is higher than this level, the drive will wake up after the
time set up in P8-17 has elapsed. The delay timer will reset to 0 if the feedback goes below this level in the meantime.
If P8-14 = 2:
If the level of Analogue Input 1 is higher than this level, the drive will wake up after the time set up in P8-17 has elapsed. The delay timer
will reset to 0 if Analogue Input 1 goes below this level in the meantime.
If P8-14 = 3:
If the DC Bus Voltage is higher than this level, the drive will wake up after the time set up in P8-17 has elapsed. The delay timer will reset to
0 if the DC Bus Voltage goes below this level in the meantime.
P8-17
Standby Wake-up Delay Time
0.0
250.0
0.0
s
This delay works in conjunction with P8-16 when the drive wakes up from a standby condition.
P8-18
MPPT Controller Minimum Voltage
0
-
-
V
This parameter defines the minimum DC Bus voltage at which the MPPT controller will operate at. When the DC Bus voltage is below
the level set in this parameter, the MPPT will not be active. This parameter also sets the array voltage that the drive will enter low power
standby mode if P8-13 is greater than 0.
P8-19
MPPT Controller Maximum Voltage
0
-
-
V
This parameter defines the maximum DC Bus voltage at which the MPPT controller will operate at. When the DC Bus voltage is above the
level set in this parameter, the MPPT will not be active.
P8-20 MPPT Controller Voltage Steps
1
30
5
V
This parameter defines the voltage steps for the MPPT controller. Setting a high value here will make the MPPT controller respond quicker
but with a lower resolution. Setting a lower value will give higher resolution but with a slower response.
9.5.4. Parameter Group 9 – User Inputs and Output Programming
Par.
Function
Setting Range
Default
Notes
P9-01
Enable Input Source
These parameters allow the user to directly select the source of the various command points.
Parameters are only adjustable if P1-13 = 0. This allows complete flexibility over the drive
control functions, and interaction with the internal Function Block programming environment.
P9-02
Fast Stop Source
P9-03
Run Forward Source
P9-04
Run Reverse Source
P9-05
Latch Enable
0
Disabled
0
1
Enabled
P9-06
Reverse Input Source
See above
P9-07
Reset Source
P9-08
External Trip Source
P9-09
Terminal Control Overide Source
P9-10
Speed Source 1
In combination with P9-18 – P9-20, allow selection of several speed reference sourcesfor
common applications.
P9-11
Speed Source 2
P9-12
Speed Source 3
P9-13
Speed Source 4
P9-14
Speed Source 5
P9-15
Speed Source 6
P9-16
Speed Source 7
P9-17
Speed Source 8
P9-18
Speed Select Input 0
See above
P9-19
Speed Select Input 1
P9-20
Speed Select Input 2
P9-21
Preset Speed Select Input 0
P9-22
Preset Speed Select Input 1
P9-23
Preset Speed Select Input 2
P9-28
MOP Up Source
P9-29
MOP Down Source
9