Range Min
and
Range Max
determine the range of the sensor for the input measuring
range.
The
Conversion…
fields
set the conversion parameters of the measured value
(Sensor_Value) to final value (Final_Value).
The
Unit
field allows adding a unit to the final value of the measured signal.
8.3
Setting the alarms
The device can compare the measured value with the thresholds set by the user.
Detection of value violation is treated as an alarm. The alarm status is available as virtual
input and for most protocols.
The alarm can be configured for the following cases (Alarm mode):
•
Disabled –
the alarm disabled
•
Low –
the alarm is active if the measured value is smaller than the value set in
the field
Alarm Low Value
.
•
High –
the alarm is active if the measured value is higher than the value set in
the field
Alarm High Value
.
•
Low + High –
the alarm is active if the measured value is higher than the value
in the field
Alarm High Value
or lower than the value
Alarm
Low Value
.
The occurrence of an alarm condition is signaled by a flashing LED display on the device.
During the alarm, the virtual output 1 is activated in the status.xml resource
http://192.168.111.15/status.xml
<on>00000001</on>
)
<
response
>
<
prod_name
>
Nano-AN
</
prod_name
>
<
sv
>
0.9
</
sv
>
<
mac
>
D0:00:00:00:00:00
</
mac
>
<
on
>
00000001
</
on
>
<
valFinal
>
2.49
</
valFinal
>
<
unitFinal
>
m
</
unitFinal
>
<
valSensor
>
2.49
</
valSensor
>
<
unitSensor
>
mA
</
unitSensor
>
<
inputType
>
0
</
inputType
>
<
valScale10000
>
2338
</
valScale10000
>
<
valScale1000
>
233
</
valScale1000
>
<
valScale100
>
23
</
valScale100
>
<
iu
>
7.735
</
iu
>
</
response
>
If the SNMP service has been configured, the device can send
TRAP
to the IP address.
User manual Nano Analog PoE v2
Page
18
of
32
[B01]