background image

User manual

Analog input converter

LAN/RS485

Nano Analog PoE

Soft >= 0.9

User manual Nano Analog PoE v2

 

Page

 

1

 of 

32

[B01]

Содержание Nano Analog PoE

Страница 1: ...User manual Analog input converter LAN RS485 Nano Analog PoE Soft 0 9 User manual Nano Analog PoE v2 Page 1 of 32 B01...

Страница 2: ...e the basic principles of safety and maintenance Please also keep the user manual so that you can read it during later use Attention The manufacturer is not liable for any damage caused by improper us...

Страница 3: ...ECURITY SETTINGS AND ADMINISTRATION 14 7 SENSOR SIGNAL CONVERSION FLOW 15 8 THE DEVICE FUNCTIONS 17 8 1 THE DEVICE STATUS 17 8 2 CONFIGURATION OF THE ANALOG INPUT 17 8 3 SETTING THE ALARMS 18 8 4 SERV...

Страница 4: ...could cause injury or damage to the device Important information and guidelines Following this guidelines makes the use of the device easier Attention The screenshots in this manual can be dissimilar...

Страница 5: ...oducing the device on the market The warranty covers all defects in material and workmanship The manufacturer undertakes to comply with the contract of guarantee if the following conditions are met al...

Страница 6: ...C relative humidity from 30 to 75 atmospheric pressure from 700 to 1060hPa Recommended transport conditions surrounding temperature from 40 C to 85 C relative humidity from 5 to 95 atmospheric pressur...

Страница 7: ...ution 17 bit Input parameters in current mode Measurement range 0 20mA or 4 20mA Maximum input current 25mA Input impedance 1R Measurement error 0 8 Input parameters in voltage mode Measurement range...

Страница 8: ...h voltage output 0 5V sensors with voltage output 0 10V sensors with current output 4 20mA sensors with current output 0 20mA The user can configure the method of transformation the measured value by...

Страница 9: ...is equipped with an LED display on which the currently measured value is displayed 5 3 Description of the module connectors The module is equipped with the following connectors LAN connection of LAN a...

Страница 10: ...5 4 Sensor connecting schematics Voltage output sensors 0 10V or 0 5V Current output sensor 0 20mA or 4 20mA User manual Nano Analog PoE v2 Page 10 of 32 B01...

Страница 11: ...terface list box and click on Change IP button In a new opened dialog box settings such as IP address MASK GATEWAY DNS1 DNS2 and the Host name can be changed Please save correct settings by choosing C...

Страница 12: ...et Network Connections choose the related controller and right click on Properties After selecting this option configuration window will show up Next choose Internet Protocol TCP IP double click on it...

Страница 13: ...ress of the reader IP Mask IP subnet mask Gateway network gateway DNS1 DNS2 DNS servers addresses Destination IP the IP address of the server or of the external device in the M2M connection chapter 8...

Страница 14: ...rator password in Current Password value field write a current password Next in appropriate value field New Password write your new password and confirm it at Re type Password value field Admin Passwo...

Страница 15: ...hermometer sensor with current output 4 20mA and measured range from 50 C to 100 C The rangeMin is set to 50 and rangeMax is set to 100 The Sensor_Value variable show 50 for 4mA and 100 for 20mA The r...

Страница 16: ...n_multiplier 0 394 1 2 54 0 394 Conversion_final offset 0 With such coefficients the Final_Value value will be corrected for error and reported in inches The Scale10000 Scale1000 and Scale100 values a...

Страница 17: ...et thresholds 8 2 Configuration of the analog input The Input tab is to configure the input type and signal conversion method Before configuring it is recommended to read the chapter Sensor signal con...

Страница 18: ...e alarm is active if the measured value is higher than the value set in the field Alarm High Value Low High the alarm is active if the measured value is higher than the value in the field Alarm High V...

Страница 19: ...les Modbus RTU RS485 server Enable SNMP enables SNMP protocol supporting Enable Destination Client connecting to a remote host service chapter 8 5 Enable MQTT Inveo a service that sends data to the IN...

Страница 20: ...rvice enter the Administration tab and select Enable Program Access and confirm with the Save Config button Configuration of devices sending alarm status messages To enable the service enter the Admin...

Страница 21: ...form An example TCP frame sent with active alarm and Dest 5 set SOF CMD CH F_ID ALARM ALARM Val0 LSB Val1 Val2 Val3 MSB CRC 0x0F 0x01 0x04 0xFF 0x01 0xFE 0x0F 0x00 0x01 0x57 0x79 An example TCP frame...

Страница 22: ...n alarm is active 0 means an alarm is inactive Final_Val Final_Val value Value in HEX STRING 35 34 31 30 45 43 36 35 35 30 32 31 20 30 20 34 36 2E 39 5410EC655021 0 46 9 The TCP frame can be supported...

Страница 23: ...Save link as option Download the file to the MIB Browser program The basic parameters that can be read from the Nano Analog PoE module can be found in the table Name Format OID Final_Val STRING 1 3 6...

Страница 24: ...ss 192 168 111 15 and listens on port 9761 TCPRel in 1 host 192 168 111 15 port 9761 analog 8 9 Linux control program The module s input status can be read from the command line of the Linux system To...

Страница 25: ...e RS485 port The Modbus configuration is available via the Administration tab To enable the Modbus protocol check the Enable Modbus TCP or Enable Modbus RTU field Configuration of RS485 port The optio...

Страница 26: ...s that is all possible separately for Long integer and Float floating point values For example for Long a decimal number 512002 has a hexadecimal value 00 07 D0 02 Representation of the number in diff...

Страница 27: ...ciowy skalowany do warto ci 0 1000 6 Scale100 R Sygna wej ciowy skalowany do warto ci 0 100 Long values 32 bit 10 ADC_Value R Warto z przetwornika 11 12 Final_Value x1000 R Warto finalna 1000 13 14 S...

Страница 28: ...very 1 minute and additionally at each change Application configuration MQTT client Address mqtt inveo com pl Port 1883 User name nanouser User password nanouser Topic nanoA MAC After click Show Info...

Страница 29: ...e Nano TC prod_name sv 0 9 sv mac 00 00 00 00 00 00 mac on 00000000 on valFinal0 3 13 valFinal0 unitFinal0 C unitFinal0 valFinal1 22 99 valFinal1 unitFinal1 C unitFinal1 response Section Description p...

Страница 30: ...e communication protocol Nano TC Sensor communication data frame Command Byte number 1 2 3 4 5 6 7 8 9 10 11 Byte name SOF CMD Channel Data1 Data2 Data3 Data4 Data5 Data6 Data7 CRC Returns Temperature...

Страница 31: ...ort TCP 502 Support via SNMP protocol port UDP 161 10 Checking the IP address To check the current IP address of the device 1 Press and hold the reset button until the display shows the four parts of...

Страница 32: ...o update the software check the Enable TFTP Bootloader option which is located in the Administration tab run the Windows command line Start Run enter cmd and confirm with the Enter key go to the direc...

Отзывы: