10.5 Multi-function board instruction (This multi-function board is optional)
10.5.1. Function
The multi-function board receives the signal of 4-cored wired controller(central
controller),Non-polar wired controller and CP remote on-off signal( ON-OFF command
signal). Then converting it to the communication signal to the main control board.
The multi-function board can output Alarm signal.
The multi-function board has two versions, one for Non-polar wired controller, the other one
for 4-cored wired controller or central controller.
10.5.2. CP remote on-off
10.5.2.1 This is the same as the LCAC, that is to say for the first time, when you active this
function, you need firstly use remote controller to turn on the unit .After setting, when the
unit are running, you can use the on-off function to turn off the units and display will show
CP, when you use this function again, the display will cancel CP and the unit will run as the
last situation.
10.5.2.2 If need this function, the switches F2 should be settled as below:
Dip-switch 2
Dip-switch 1
Remote on-off control status
OFF
OFF
Disconnected send CP, closed cancel CP
ON
OFF
Closed send CP, disconnected cancel CP
10.5.3. ON-OFF control
10.5.3.1 With on-off command, you can directly use this function regardless remote
controller.The indoor will be turned on and off by this port. But indoor will still get order from
remote controller when it is turned off by this port. when the indoor is turned on by this port,
the unit will run in Auto mode ,Auto fan speed, 24
℃
setting temperature
10.5.3.2 If need this function, the switches F2 should be settled as below:
Dip-switch 2
Dip-switch 1
Remote on-off control status
OFF
ON
Disconnected send ON, closed send OFF
ON
ON
Closed send OFF
,
disconnected send ON
10.5.4. 4-cored wired controller
,
Central controller and Non-polar wired controller
Note: 4-cored wired controller, Central controller and Non-polar wired controller
are mutually exclusive. They can only be chosen one of three at the same time.
10.5.4.1 For network address, Dip-switch F1 and Rotary switch ENC3 are set as below:
Dip-switch 2
Dip-switch 1
Based address
OFF
OFF
0
OFF
ON
16
ON
OFF
32
ON
ON
48
Содержание P8MVI32-09WiFi
Страница 2: ......
Страница 14: ...12 For P8MVI32 09WiFi For P8MVI32 09WiFi P8MVO32 09 P8MVI32 12WiFi P8MVO32 12...
Страница 15: ...13 For P8MVI32 18WiFi P8MVO32 18 For P8MVI32 24WiFi P8MVO32 24...
Страница 19: ...17 For P8MVO32 24...
Страница 34: ...32 8 Wiring Diagram 8 1 Indoor Unit P8MVI32 09WiFi P8MVI32 12WiFi P8MVI32 18WiFi P8MVI32 24WiFi...
Страница 35: ...33 8 2 Outdoor Unit P8MVO32 09 P8MVO32 12 P8MVO32 18 P8MVO32 24...
Страница 70: ...68...
Страница 71: ......
Страница 72: ...Scan here to download the latest version of this manual WALL MOUNTED UNIT AIR CONDITIONING SYSTEMS...