7
2.3 Effluent quality approval
During the certification process the INTEWA AQUALOOP System Greywater Recycling produces an
effluent that successfully met the performance requirements established by NSF/ANSI Standard 350 Class
C for a multi-family or commercial location:
Measure
NSF/ANSI 350
Class C
requirement
Class C
AQUALOOP test result NSF approval
Certificate No.: C0241944 - 01
Measure
Test
Average
Single
Sample Maximum
Result
Average
Single
Sample Maximum
CBOD
5
(mg/L)
10
25
6
17
TSS (mg/L)
10
30
2
8
turbidity (NTU)
2
5
0.5
1
4.0
E. coli
2
(MPN/100
mL)
2.2
2
200
2.0
2
13.0
pH (SU)
6.0 – 9.0
NA
3
6.7 – 8.0
NA1
color
MR
2
NA
3
MR
4
NA1
odor
Non offensive
NA
3
Non offensive
NA1
oily film and foam
Non-detectable
Non-detectable
Non-detectable
Non-detectable
1 median, 2 geometric mean, 3 NA: not applicable, 4 MR: measured and reported only
Tab: Effluent requirement and certification test results for AQUALOOP
Fig.: Tested AQUALOOP model AL-GW300 (with one equipped membrane cartridge)
Содержание AQUALOOP GW 10800
Страница 10: ...9 Tab Official listing https www intewa de en applications rain greywater harvesting greywaterrecycling...
Страница 12: ...11 Fig AQUALOOP System 1200 L day 317 GPD Fig AQUALOOP System 1800 L day 476 GPD...
Страница 13: ...12 Fig AQUALOOP System 3600 L day 952GPD Fig AQUALOOP System 5400 L day 1428 GPD...
Страница 37: ...36 Fig Electrical connection plan upper pump lower pump...
Страница 39: ...38 Fig Control cabinet of multiple membrane station controller...
Страница 42: ...41 7 1 3 Expansion membrane station controller Fig Control cabinet of expansion controller...
Страница 89: ...88 Designed and provided by INTEWA GmbH or to be separately approved alternative...
Страница 90: ...89 INTEWA GmbH Version 1 1 a Subject to technical changes...