35
Item Connection
Description
Connecting contact/Function
1
ADr Pump
Analogue pressure sensor for filtration and
backwash pump monitoring
Sig
= green
GND = gray
Ub + = brown
2
ADg Air
Analogue pressure sensor for blower
monitoring (2-wire)
Sig
= black (Pin 2)
Ub + = brown (Pin1
3
Float Sw
BR min
Floating switch in bioreactor for minimum
water level
Pot. free contact, normally open contact,
no polarity
4
Float Sw
CL max
Floating switch in clear water tank for
maximum water level
Pot. free contact, normally open contact,
no polarity
5
Float Sw
CL_min
Floating switch in bioreactor for maximum
water level
Pot. free contact, normally open contact,
no polarity
6
Float Sw
CL_min out
No function--
--
7
Pump
Suction
24 V DC pump for filtration process (lower
pump!)
GND = blue
+ = brown
8
Pump
Backflush
24 V DC pump for backwash process (upper
pump!)
GND = blue
+ = brown
9
Air
Only for use with a 24 V DC blower
(alternative to 230V blower) or 24 V DC
solenoid valve (back wash nozzle for pre-
filter)
Blower:
GND = blue
+ = brown
Solenoid valve:
GND = pin 1
+ = pin 2
10
230V- Air
Blower
Max. switching voltage = 400V AC
Rated voltage = 250 V AC
Rated current = 12A
PE = Green/yellow
N = blue
L = brown
11
230V-Sludge
Sludge pump
Max. switching voltage = 400V AC
Rated voltage = 250 V AC
Rated current = 12A
PE = Green/yellow
N = blue
L = brown
12
230V-IN
Mains for switching voltage
110- 230 V AC / 50-60 Hz
PE = Green/yellow
N = blue
L = brown
13
24 V DC
Switching power supply:
IN: 110- 230 V AC / 50-60 Hz
OUT: 24 V DC, 4A
Stereo jack
Ø5.5mm, Centre positive
14
Cable bridge
For activation of rechargeable battery and
switching power supply
(install cable bridge during start-up
installation, s. section 6.1)
4-pin plug ,
reverse-polarity protected
15
9V
rechargeable
battery
9 V battery, 200 mA, NIMH
Attention: Only a rechargeable battery can
be used when changing the internal battery!
Pay attention to polarity while changing
16
6-pin
6-pin programmed connection
(for update programming)
Pay attention to polarity
17
DIL
DIL switch
Factory setting 1 = ON
Factory setting 2 = OFF
1=ON : Alarm* with battery operation ON
1=OFF : Alarm with battery operation OFF
2=ON /Off: without function
* A short beep sounds at an interval of 5
seconds indicating the battery is being used!!
Tab.: Connection description of control board
Содержание AQUALOOP GW 10800
Страница 10: ...9 Tab Official listing https www intewa de en applications rain greywater harvesting greywaterrecycling...
Страница 12: ...11 Fig AQUALOOP System 1200 L day 317 GPD Fig AQUALOOP System 1800 L day 476 GPD...
Страница 13: ...12 Fig AQUALOOP System 3600 L day 952GPD Fig AQUALOOP System 5400 L day 1428 GPD...
Страница 37: ...36 Fig Electrical connection plan upper pump lower pump...
Страница 39: ...38 Fig Control cabinet of multiple membrane station controller...
Страница 42: ...41 7 1 3 Expansion membrane station controller Fig Control cabinet of expansion controller...
Страница 89: ...88 Designed and provided by INTEWA GmbH or to be separately approved alternative...
Страница 90: ...89 INTEWA GmbH Version 1 1 a Subject to technical changes...