10
STEP #4
SNAP THE MULTIPURPOSE CONTROL
INTO THE INTERMATIC PANEL
IMPORTANT NOTE
Since you have easy access to the back of the
Multipurpose Control, make sure you properly set
the source voltage selector jumper to the voltage
(i.e. 120V or 240V), you intend to use for powering
the Multipurpose Control. This jumper is located on
the back of the control (See Figure #1 for location
and setting).
Installation Procedure
1. Rotate the Multipurpose Control mechanism until the
Tabs line up with the Slots. Slide the bottom half in
the Slots, and push the top half into the Bracket until
the mechanism snaps into the Bracket Slot.
Figure #4
Bracket
Tabs
Slots
Bracket Slot
STEP #10
Setting Freeze Protection
NOTE
The freeze protection programming will not appear
unless you have installed the Intermatic freeze
sensor,
(See Fig. #1 for installation and ordering details).
Without the freeze sensor installed, programming will
end once you have finished programming the cool
down cycle, and pressed and released the Program
key to advance.
1. Use the program key to save and advance to the
Freeze
setting.
The 1st circuit is the factory selected default.
2. Use the Up and Down arrow keys to switch between
Freeze Protection ON and OFF.
3.
Push and release the desired ON/OFF keys to
indicate which circuits should come ON when freeze
protection engages.
4. When programming is complete, push and release
the Enter key or Program key to end your program-
ming session.
If the clock has freeze protection turned ON and the probe goes bad or
the cable is cut/removed, the pump will turn on and continue to run as if
a freeze condition exists. Preselected circuits will activate and FREEZE will
be displayed. At this point, the time switch
stops
running the programmed
schedule. To restore normal operation the probe must be replaced.
To temporarily restore normal operation press the ON/OFF button for the
circuit(s) that is active. “Freeze” will begin to flash to indicate that freeze
protection is over ridden and the clock will follow the programmed schedule.
(NOTE: if there is a power outage, when power is resumed the clock will go
back into freeze mode).
OFF
31