intensity IC4H-04KF-3 Скачать руководство пользователя страница 9

8

Owner’s & Installation manual 

6.2   Drainage test 

Check whether the drainpipe is unhindered 

New built house should have this test done before paving  
the ceiling. 

1  Remove the test cover, and stow water of about 2000ml  
to the water receiver through the stow tube.  

2  Turn on the power, and operate the air conditioner  
under the "COOLING" mode. Listen to the sound of the  
drain pump. Check whether the water is discharged well (a  
lag of 1min is allowed before discharging, according to the  
length of the drain pipe), and check whether water  
leaksfrom the joints. 

CAUTIONS: If there is any malfunction, please resolve it  
immediately. 

3  Stop the air conditioner for there minutes, check if  
everything is ok. If the drain hose is located unreasonable,  
water overflow will cause the Alarm indicator lamp flashing  
(For both cooling and heating type or cooling only type),  
even the water leak out from the water receiver. 

4  Check the drain pump whether drain water immediately  
when alarm sound for the high water lever. If the water  
lever can't come down below to the limited water lever, the  
air conditioner will stop. Restart it until  turn off the power  
and drain off all the water. 

5  Turn off the power, drain the water away. 

The drain plug is used to empty the water-receiver for maintenance  
of the air conditioner. Please stuff it imposition at all times during  
operation to avoid leakage. 

Dissemble the bolts from the cover.(If there isn't a cover on  
the outdoor unit, disassemble the bolts from the maintenance  
board, and pull it in the direction of the arrow to remove the  
protection board.) 

Connect the connective cables to the terminals as identified  
with their respective mached numbers on the terminal block  
of indoor and outdoor units. 

Re-install the cover or the protection board. 

Connect the cable 

7.1 

7.    WIRING

CAUTION 

NOTE

The power connection for the air conditioner has to be  
done at the main power distribution. The distribution has  
t o  b e  o f  al o w  i m p e d a n c e ,  n o r m a l l y  t h e  r e q u i r e d   
impedance reaches at a 32 A fusing point. 

No other equipment has to be connected with this power  
line. 

For detailed installation acceptance please refer to your  
power supplier, if restrictions do apply for products like  
washing machines, air conditioners or electrical ovens.  

For power details of the air conditioner refer to the rating  
plate of the product.  

For any question contact your local dealer. 

Remark per EMC Directive 2004/108/EC 
For to prevent flicker impressions during the start of the  
compressor (technical process), following installation  
conditions do apply. 

The air conditioner should use separate power supply 
with rated voltage. 
 
The external power supply to the air conditioner should 
have ground wiring, which is linked to the ground wiring of 
the indoor and outdoor unit. 
 
The wiring work should be done by qualified persons 
according to circuit drawing. 

 
an all-pole disconnection device which has at least 3mm 
separation distance in all pole and a residual current 
device(RCD)with the rating of above 10mA shall be incorpo-
rated in the fixed wiring according to the national rule. 
 
The appliance shall be installed in accordance with national 
wiring regulations. 
 

Be sure to locate the power wiring and the signal wring 
well to avoid cross-disturbance. 
 
Do not turn on the power until you have checked 
carefully after wiring.   

four-way cassette:

four-way cassette:

four-way cassette:

slim four-way cassette:

slim four-way cassette:

slim four-way cassette:

0.8~1.0 m

a  

>1.0 m

b

 Fig.6-1

Gradient: 
higher than 1/100

b

<200mm

Lean over 1/100

Pump-pipe clasp

 (the fittings)

0.8-1.0m

Fig.6-2

Max. 1000mm

<200mm

Lean over 1/100

Pump-pipe clasp

 (the fittings)

0.8-1.0m

Max. 600mm

four-way cassette:

slim four-way cassette:

0.8~1.0 m

a  

>1.0 m

b

 Fig.6-1

Gradient: 
higher than 1/100

b

<200mm

Lean over 1/100

Pump-pipe clasp

 (the fittings)

0.8-1.0m

Fig.6-2

Max. 1000mm

<200mm

Lean over 1/100

Pump-pipe clasp

 (the fittings)

0.8-1.0m

Max. 600mm

four-way cassette:

four-way cassette:

four-way cassette:

slim four-way cassette:

slim four-way cassette:

slim four-way cassette:

0.8~1.0 m

a  

>1.0 m

b

 Fig.6-1

Gradient: 
higher than 1/100

b

<200mm

Lean over 1/100

Pump-pipe clasp

 (the fittings)

0.8-1.0m

Fig.6-2

Max. 1000mm

<200mm

Lean over 1/100

Pump-pipe clasp

 (the fittings)

0.8-1.0m

Max. 600mm

Содержание IC4H-04KF-3

Страница 1: ...MAN ICC4H 1112 Compact Four Way Cassette Chilled Water INSTALLATION OWNER S MANUAL www intensity com mx IC4H 04KF 3...

Страница 2: ...ries parts and specified parts for installation otherwise it will cause the set to fall water leakage electrical shock and fire The appliance must be installed 2 3m above floor The appliance shall not...

Страница 3: ...all the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise Depending on the radio waves...

Страница 4: ...n sheath 8 Out let pipe clasp 7 Out let pipe sheath 6 Out let pipe pipe 9 Tightening band 14 Installation owner s manual 15 Remote controller manual 10 Remote controller 11 Frame 12 Mounting screw ST2...

Страница 5: ...ceiling are even The body s lower part should sink into the ceiling for 10 12 mm refer to fig 5 6 In general L is half of the screw length of the installation hook refer to fig 5 6 Locate the air cond...

Страница 6: ...g point of drain pipe 840 Body 950 Panel 330 Drain side Drain side Drain side Tubing side Unit mm Unit mm Unit mm 780 Hook location 780 Hook location 780 Hook location 840 Body 840 Body 840 Body 950 P...

Страница 7: ...ers to choose Type H mm Four way cassette Four way cassette compact 45 50 Height of the front panel Ceiling 600mm ceiling hole Ground 261 213 Panel Inlet Outlet Outlet Water pipe joint Connecting poin...

Страница 8: ...THE DRAIN PIPE 7 6 1 Install the drain pipe of indoor unit 1 The drainpipe can use PVC pipe external diameter about 37 39mm inner diameter is 32mm 2 Joint drainpipe connector to the end side of water...

Страница 9: ...her equipment has to be connected with this power line For detailed installation acceptance please refer to your power supplier if restrictions do apply for products like washing machines air conditio...

Страница 10: ...The ground wiring is connected correctly The length of the tubing has been recorded The power voltage fits the rated voltage of the air conditioner There is no obstacle at the outlet and inlet of the...

Страница 11: ...ds the middle simultaneously as indicated in fig 9 1 Then pull down the air in grill The control box cables which are originally connected with the main body electrical terminators must be pulled off...

Страница 12: ...s in order to shelter from sunshine Reduce heat source AC cooling capacity reduces normal Check leakage Symptoms Causes Unit does not start Air flowing normally but completely can t cooling Units star...

Страница 13: ...f the remote controller to the infrared signal receiver of the indoor unit and then repeatly push the ON OFF button twice The indication on the display disappears after a lapse of time Check whether t...

Страница 14: ...O Malfunction running lamp timer lamp defrosting lamp alarm lamp 1 2 3 4 5 Room temperature sensor checking channel is abnormal Evaporator sensor checking channel is abnormal EEPROM malfunction Water...

Страница 15: ......

Отзывы: