Owner’s & Installation manual 

5.4   Install The Panel 

Remove the air-in grill. 

CAUTION 

Never put the panel face down on floor or against the  
wall, or on bulgy objects. 

Never crash or strike it. 

Do not coil the wiring of the swing motor into the seal  
sponge. 

CAUTION 

Slide two grill switches toward the middle at the same time,  
and then pull them up.  

(Refer to fig.5-9) 

Draw the grill up to an angle of about 45, and remove it.  

(Refer to fig.5-10) 

Remove the installation covers at the four corners 

Wrench off the bolts, loose the rope of the installation covers,  
and remove them.  

(Refer to fig.5-11) 

Install the panel 

Align the swing motor on the panel to the tubing joints of the  
body properly.  

Fix hooks of the panel at swing motor and its opposite sides  
to the hooks of corresponding water receiver. Then hang the  
other two panel hooks onto corresponding hangers of the  
body. 

Adjust the four panel hook screws to keep the panel  
horizontal, and screw them up to the ceiling evenly.  

Regulate the panel in the direction of the arrow  slightly to fit  
the panel's center to the center of the ceiling's opening.  
Guarantee that hooks of four corners are fixed well. 

Keep fastening the screws under the panel hooks, until the  
thickness of the sponge between the body and the panel's  
outlet has been reduced to about 4~6mm. The edge of the  
panel should contact with the ceiling well.     

Fasten the rope of installation cover on the bolt of the  
installation cover.  

Press the installation cover into the panel slightly.  

 If the gap between the panel and ceiling still exists after  
fastening the screws, the height of the indoor unit should  
be modified again.  

You can modify the height of the indoor unit through the  
openings on the panel's four  corners, if the lift of the  
indoor unit and the drainpipe is not influenced  

Hang the air-in grill to the panel, then connect the lead  
terminator of the swing motor and that of the control box  
with corresponding terminators on the body respectively. 

Relocate the air-in grill in the procedure of reversed order. 

Relocate the installation cover. 

6.    CONNECT THE DRAIN PIPE

7

6.1 Install the drain pipe of indoor unit 

 
1) The drainpipe can use PVC pipe (external diameter about 37

39mm, inner diameter is 32mm).  
 
2) Joint drainpipe connector to the end side of water pumping pipe, 
and fix drainpipe together with water outflow pipe and thermal 
insulation tube by clasp of water outflow pipe (attached).   

CAUTION 

Don’t use forcing strength to crack the water-pumping pipe.  

3) Water-pumping pipe and drainpipe from main body must be 
wrapped by insulation tube evenly, and bound by tighten band for 
obstructing air getting in and coagulation. 
 
4) Prevent from water backflow into unit inside during shutdown, 
the drain pipe shall place down side and drain water to outdoor 
(drain side), the gradient of the drain pipe should be higher than 
(1/100), without salient and water remain.(

Refer to

 

Fig.6-1 a

 
5) When connecting drainpipe, don’t drag the pipe that would pull 
the main unit. For this, please arrange bearing points every 0.8 to 
1.0 meter to avoid pipe be bended (See 

Fig.6-1 b

). 

 
6) When connect a lengthen drainpipe, apply protective tube to 
wrap its indoor parts for ensuring the lengthen part connected 
tightly.    
 
7) In case the drainpipe outlet is higher than pumping connective 
pipe of the main body, the drainpipe must be arranged upwards 
vertically by using connective assembly of the water outlet for 
vertical bending, and the height of the drainpipe shall set to the 
defrosting pan surface no more than 1000mm (four-way cassette) 
or 600mm (slim four-way cassette) , otherwise, too much backflow 
while shutdown would leads to overflow (Refer to Fig.6-2). 
 
8) Base on the actual requirement to bend piping, and use 
connective assembly of water outlet in terminal box for pipe layout. 

CAUTION 

The joints in drain system must be sealed to avoid water leakage. 

9) The height from floor to the end of drainpipe or the bottom of 
drain slot must more than 50 mm. Don’t immerse the end of 
drainpipe or the bottom of drain slot into water. When drain 
condensate liquid to raceway, please bend the drainpipe to a 
U-sharped hydroseal for avoiding stench transmitted by drainpipe 
to indoor.        

All the pictures in this manual are for explanation  
purpose only. They may be slightly different from the air  
conditioner you purchased(depend on model).The  
actual shape shall prevail. 

NOTE 

Содержание IC4H-04KF-3

Страница 1: ...MAN ICC4H 1112 Compact Four Way Cassette Chilled Water INSTALLATION OWNER S MANUAL www intensity com mx IC4H 04KF 3...

Страница 2: ...ries parts and specified parts for installation otherwise it will cause the set to fall water leakage electrical shock and fire The appliance must be installed 2 3m above floor The appliance shall not...

Страница 3: ...all the indoor and outdoor units power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise Depending on the radio waves...

Страница 4: ...n sheath 8 Out let pipe clasp 7 Out let pipe sheath 6 Out let pipe pipe 9 Tightening band 14 Installation owner s manual 15 Remote controller manual 10 Remote controller 11 Frame 12 Mounting screw ST2...

Страница 5: ...ceiling are even The body s lower part should sink into the ceiling for 10 12 mm refer to fig 5 6 In general L is half of the screw length of the installation hook refer to fig 5 6 Locate the air cond...

Страница 6: ...g point of drain pipe 840 Body 950 Panel 330 Drain side Drain side Drain side Tubing side Unit mm Unit mm Unit mm 780 Hook location 780 Hook location 780 Hook location 840 Body 840 Body 840 Body 950 P...

Страница 7: ...ers to choose Type H mm Four way cassette Four way cassette compact 45 50 Height of the front panel Ceiling 600mm ceiling hole Ground 261 213 Panel Inlet Outlet Outlet Water pipe joint Connecting poin...

Страница 8: ...THE DRAIN PIPE 7 6 1 Install the drain pipe of indoor unit 1 The drainpipe can use PVC pipe external diameter about 37 39mm inner diameter is 32mm 2 Joint drainpipe connector to the end side of water...

Страница 9: ...her equipment has to be connected with this power line For detailed installation acceptance please refer to your power supplier if restrictions do apply for products like washing machines air conditio...

Страница 10: ...The ground wiring is connected correctly The length of the tubing has been recorded The power voltage fits the rated voltage of the air conditioner There is no obstacle at the outlet and inlet of the...

Страница 11: ...ds the middle simultaneously as indicated in fig 9 1 Then pull down the air in grill The control box cables which are originally connected with the main body electrical terminators must be pulled off...

Страница 12: ...s in order to shelter from sunshine Reduce heat source AC cooling capacity reduces normal Check leakage Symptoms Causes Unit does not start Air flowing normally but completely can t cooling Units star...

Страница 13: ...f the remote controller to the infrared signal receiver of the indoor unit and then repeatly push the ON OFF button twice The indication on the display disappears after a lapse of time Check whether t...

Страница 14: ...O Malfunction running lamp timer lamp defrosting lamp alarm lamp 1 2 3 4 5 Room temperature sensor checking channel is abnormal Evaporator sensor checking channel is abnormal EEPROM malfunction Water...

Страница 15: ......

Отзывы: