The Proper Installation & Maintenance of LPI-LCD-6. 

THE LPI-LCD-6 IS TO BE INSTALLED AND SERVICED BY SERVICE PERSONNEL ONLY. NO OPERATOR / USER 

SERVICEABLE PARTS. 

All power and signals must be de-energised before connecting any wiring. Also refer to LPI-LCD-6 Layout &  

Dimensions. 

 

Mounting. 

1)  Make sure the surface of the mounting is clean before installing. 

2)  Do not subject to vibration or excess temperature or humidity variations. 

3)  Avoid mounting on cabinets with power control equipment. 

4)  To maintain compliance with the EMC Directives the LPI-LCD-6 is to be mounted on steel cabinet that must be 

properly earthed, with appropriate input/output entry points and cabling. 

5)  Allow 10mm minimum clearance between the LPI-LCD-6 terminals and ANY conductive material. 

 

Wiring. 

1)  All cables should be good quality overall screened INSTRUMENTATION CABLE with the screen earthed at one 

end only. 

2)  Signal cables should be laid a minimum distance of 300mm from any power cables. 

3)  For 2 wire current loops and 2 wire voltage signals or 2 wire current signals, Austral Standard Cables B5102ES is 

recommended. For 3 wire transmitters Austral Standard Cables B5103ES is recommended. 

4)  It is recommended that you do not ground current loops and only use power supplies with ungrounded outputs. 

5)  Lightning arrestors should be used when there is a danger from this source. 

6)  Refer to ‘Terminal Layout’ diagrams above for connection information. 

 

Commissioning. 

1)  Once all the above conditions have been carried out and the wiring checked apply power to the LPI-LCD-6 loop and  

allow five minutes for it to stabilize. 

2)  Take a low reading (approx. 10%) and high reading (approx. 90%) of the variable being measured by the  

transducer supplying the signal to the LPI-LCD-6, and ensure that this agrees with the level being indicated by the 

PLC or indicator, etc., that the LPI-LCD-6 is connected into. Adjust for any differences. 

 

Maintenance. 

1)  Check the Sensor or Transducer supplying the signal to the LPI-LCD-6 for wear or damage and replace if defective. 

2)  Check the cables connected to the Sensor or Transducer. 

3)  Repeat (2) of Commissioning. Do it regularly - at least once per year. 

LPI-LCD-6  061221 

w w w . in t e ch . co . n z  

Christchurch Ph: +64 3 343 0646  

Auckland Ph: 09 827 1930  

Email: 

[email protected]

 

Содержание LPI-LCD-6

Страница 1: ...1 LPI LCD 6 4 20mA Panel Display Installation Guide...

Страница 2: ...rminal Layout Page 5 LPI LCD 6 Wiring Diagrams Page 5 LPI LCD 6 Buttons Display Page 5 Display Screen Page 5 LPI LCD 6 Setup Calibration Page 6 Main Menu Page 6 Changing the Decimal Place Page 6 Setti...

Страница 3: ...No liability will be accepted for errors omissions or amendments to this specification Technical data are always specified by their average values and are based on Standard Calibration Units at 25 C u...

Страница 4: ...kers to assist with installation Apply the front sticker if you are drilling from the front of the panel and back sticker if you are drilling form the back of the panel After drilling remove the insta...

Страница 5: ...out saving changes Display Screen The screen can display 1 6 characters to reflect the condition of your 4 20 input in normal operating mode The character on the right may be set up to display units a...

Страница 6: ...n after the six display digits If you selected CUSTOM use the U and D buttons to select any one letter from A Z and then press S to save and return to the operational display the custom unit you choos...

Страница 7: ...ill appear This is the amount of time that the backlight will remain on for after the L button is pressed default 3 seconds Use the U and D buttons to adjust the time from 1 9 seconds and then press S...

Страница 8: ...current signals Austral Standard Cables B5102ES is recommended For 3 wire transmitters Austral Standard Cables B5103ES is recommended 4 It is recommended that you do not ground current loops and only...

Отзывы: