background image

Customer Services (858) 578-7887 & (888) GO IN

TEC

IN

TEC

 Controls, 12700 Stowe Dr., Suite 1

0

0, Poway, CA 92064

Fax (858) 578-4633 & (888) FX IN

TEC

www.inteccontrols.com

Specification subject to change without notice.

Printed in USA 130917

Polygard® is a registered trademark of MSR

DGC3

PolyGard

® 

Digital Gas Controller

User Manual - DGC3

Page 19

             See 

3.7.10 

                 See 

3.7.6 

              Siehe 

 See 

3.7.6 

                 Analog 

Output 

3-6 

3.7.1  Service Mode 

When the service mode is active (ON) the alarms are not transmitted to the alarm relays (in case of calibration or 

service work). The service mode ON is reset automatically after 60 minutes or manually in the menu “Service 

Mode”.

Symbol Description  Default 

Status

Function 

Off 

Service Mode  Off 

Off  = Alarms activate the associated alarm relays 

On  = Alarms are not transmitted to the alarm relays 

3.7.2  Software Version 

Symbol Description  Default 

Status

Function 

DGC03-

XX 

Software 

Version 

 

XX = Software Version 

3.7.3  Maintenance Concept 

Integrated in the DGC3 system, there is a control of the maintenance intervals as required by law or by the 

customer. At commissioning or after maintenance the number of days until the next due maintenance is entered = 

Reset of the maintenance message (service phone no.). When the days counter reaches zero, the failure signal is 

activated the following morning at 9 o’clock, and the phone no. of the service technician occurs in the display. The 

remaining days until the next maintenance can be read from the menu “Maintenance in”. 
The service phone no. can be entered individually in the next menu. 

Symbol Description 

Default 

Status 

Function 

XXX 

Maintenance in 

 

Remaining days until the next maintenance 

XXX 

Maintenance interval   

Reset of the maintenance message by entering the 

number of days until the next maintenance 

0853.... 

Phone No. 

 

Input of the individual service phone no.  

Calibration AO 1 

4.0=4 mA  20 = 20.0

Analog Output 

         3 to 6

Analog Output 1 

Max.

Analog Output 

Correct     -     Error 

    0                    0 

Specifications subject to change without notice. | USA 130917 | Page 19 of 22

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

DGC3 – UserManual

Polygard® is a registered trademark of MSR | DGC3

Specifications subject to change without notice. | USA 160104 | Page 19 of 22

12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN

TEC

 | relevantsolutions.com/inteccontrols

DGC3 – UserManual

PolyGard

®

 is a registered trademark of MSR-Electronic GmbH | DGC3

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | USA 200211 | Page 19 of 22

DGC3 – UserManual

Содержание PolyGard DGC3

Страница 1: ...ual July 2011 Specifications subject to change without notice USA 130917 Page 1 of 22 12700 Stowe Drive Suite 100 Poway CA 92064 Ph 858 578 7887 888 GO INTEC relevantsolutions com inteccontrols DGC3 U...

Страница 2: ...Mode 17 3 6 8 MP Fault Assigned to Alarm 17 3 6 9 Alarm Assigned to Alarm Relay 17 3 6 10 MP Signal Assigned to Analog Output 17 3 7 Menu System Parameters 18 3 7 1 Service Mode 19 3 7 2 Software Vers...

Страница 3: ...nd alarm threshold enable a very flexible use in the gas measuring technique Simple and comfortable commissioning is possible thanks to the configuration with preset parameters Configuration parameter...

Страница 4: ...ne relay is manually operated LED yellow Flashes at system or sensor failure or when maintenance needed LED green Power LED 2 2 Setting Changing Parameters or Set points Open desired menu window Code...

Страница 5: ...evels Starting menu Scrolling of the measuring points of all registered transmitters in 10 second intervals Main menu Submenu 1 and 2 Starting menu Main menu Submenu Display and reset of errors See fr...

Страница 6: ...fault is only possible after having removed the cause Select menu System Errors Example Communication error MP 01 1 Reset the fault Fault reset or Fault reset Cause not eliminated Reset not possible 3...

Страница 7: ...itter not calibrated defective Solution Check cable to AT transmitter perform calibration replace AT transmitter GC Error Internal communication error I O Board to LCD Board Cause Internal error Solut...

Страница 8: ...the orange red alarm LED at the Gas Controller is lit continuously The external operation of the alarm relay via an assigned digital input has priority to the manual operation in the menu Status Relay...

Страница 9: ...value of the analog transmitter Display for software version 16 bus transmitters Display for software version 8 bus transmitters and 8 analog transmitters Symbol Description Default Function MP 01 1 M...

Страница 10: ...t time for switch OFF delay See 3 5 6 Relay Mode De energized Static Flash 0 s Relay Parameter R 01 Latching Mode No Time Quitt DI 0s 0 0 External Mode DI ON 0 OFF 0 Delay ON Time 0 s Delay OFF Time 0...

Страница 11: ...ing mode active Acknowledging a latching relay in the menu Status Relay is only possible if the gas concentration is again lower than the alarm threshold including hysteresis In this case the status l...

Страница 12: ...set of the relay by push button after time having run out and when alarm is still acting relay is set again Response function Time 120 Time for automatic reset function or response function 0 no reset...

Страница 13: ...0 Mode OFF Relay is only deactivated at the end of the defined time sec 0 sec No delay 3 6 Menu MP Parameters Display and change of MP parameters including activation of measuring points and assignme...

Страница 14: ...10 Measuring range 300 ppm MP Signal Linear Threshold 1 80 ppm Threshold 2 100 ppm Threshold 3 120 ppm Threshold 4 120 ppm Hysteresis 15 ppm Delay time ON 0 s Delay time OFF 0 s C A Mode CV Alarm 1 2...

Страница 15: ...lorine Hydrogen sulphide Sulphur dioxide Carbon dioxide5 Oxygen falling 3 Ammonia Nitrogen dioxide Nitrogen oxide Combustible gas ppm Vol ppm ppm ppk r F C ppm ppm ppm ppm ppm ppm ppm ppm ppm ppm ppm...

Страница 16: ...efined with full scale value in order to avoid false alarms For O2 measurement Pay attention to the alarm activation at decreasing or increasing concentration Symbol Description Default Status Functio...

Страница 17: ...P 01 Measuring Point Selection of MP No 1 A1 A2 A3 A4 01 02 03 00 01 Alarm 1 activates alarm relay R 01 02 Alarm 2 activates alarm relay R 02 03 Alarm 3 activates alarm relay R 03 04 Alarm 4 doesn t a...

Страница 18: ...0 AV Overlay 120 s 120 ppm AV Time 1800 s Maintenance interval Days 365 Customer Pass Change Failure Relay XX Power On Time 30 s EP Module 1 Inactive EP Module 2 Inactive Specifications subject to cha...

Страница 19: ...e days counter reaches zero the failure signal is activated the following morning at 9 o clock and the phone no of the service technician occurs in the display The remaining days until the next mainte...

Страница 20: ...ring point sends the signal as defined in the menu C A Mode CV or AV Out of the signals of all assigned measuring points the Gas Controller module determines the minimum the maximum or the average val...

Страница 21: ...on of the EP 05 modules a module address is assigned to each module by the address selector See table The table shows the assignment of the relay numbers to the individual modules Symbol Description D...

Страница 22: ...latest edition of the National Electrical Code ANSI NFPA70 It is also essential to strictly follow all instructions as provided in this user manual 4 3 Maintenance It is recommended to check the PolyG...

Отзывы: