DGC3
PolyGard
®
Digital Gas Controller
User Manual - DGC3
Page 11
3.5.1 Relay Mode
Definition of relay mode:
Symbol Description Setting
Status
Function
R 01
Relay No.
Selection of relay
De-
energized Relay Mode
De-
energized
De-energized
Energized
= Alarm ON = Relay ON
= Alarm ON = Relay OFF
3.5.2 Relay Function Static / Flash
Definition of relay function
Symbol Description Setting
Status
Function
R 01
Relay No.
Selection of relay
0 Function 0
0 = Relay function static
> 0 = Relay function flashing (= Time period in sec.)
Impulse / Break = 1:1
3.5.3 Latching Mode
Definition of latching function
Symbol Description Setting
Status
Function
R 01
Relay No.
Selection of relay
No
Latching Mode No
No
Yes
= Latching mode inactive
= Latching mode active
Acknowledging a latching relay in the menu “Status Relay” is only possible if the gas concentration is again lower
than the alarm threshold including hysteresis. In this case the status latching occurs in the display.
Example: Alarm relay R2 with latching mode
Alarm 2
Display in the Menu
Status Relay
Relay 2
Reset in the Menu
Status Relay
On
Off
On
Off
On
Off
R2
Off
R2
On
R2
On
R2
On
R2
Latching
R2
Off
Gas concentration higher lower than threshold
Specifications subject to change without notice. | USA 130917 | Page 11 of 22
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
DGC3 – UserManual
Polygard® is a registered trademark of MSR | DGC3
Specifications subject to change without notice. | USA 160104 | Page 11 of 22
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC
| relevantsolutions.com/inteccontrols
DGC3 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH | DGC3
INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com
Specifications subject to change without notice. | USA 200211 | Page 11 of 22
DGC3 – UserManual