Installation instructions & user guide
T210047 v1.00 March 2022 - InstaTap Commercial
SECTION 6 Installing the under counter appliances
!
• Connect the mains plug to a 230V 50Hz 13A socket.
Before you start read :
Section 2 Important safety instructions.
Section 3 Warnings & Regulatory information.
Do not switch on the mains electricity supply until installation is complete
and all electrical /plumbing connections have been made.
6.13 Connect the electricity supply
!
I2CBC1020, I2CB10 & I2CC20 models
• Appliances rated to up to 3 KW must be connected to a 20A isolator fitted
with a suitable ELCB.
• The mains cable is supplied ready fitted to the appliance.
• Mains cable size, 2.5mm².
• Electrical installation should conform to current IEEE wiring regulations.
Mains cable wiring I2CB20 - I2CB40 models
• Appliances rated to 6.75 kW must be connected to a 30A isolator fitted
with a suitable ELCB.
• The mains cable is supplied ready fitted to the appliance.
• Mains cable size, 4.0mm².
• Electrical installation should conform to current IEEE wiring regulations.
I2CB50 models - 6.75kW configuration
I2CB50 models - 4.5kW configuration
• Appliances rated to 4.5kW must be connected to a 20A isolator fitted
with a suitable ELCB.
• The mains cable is supplied ready fitted to the appliance.
• Mains cable size, 4.0mm².
• Electrical installation should conform to current IEEE wiring regulations.