53
constant speed overcurrent
Check if the output loop
of the inverter has the short circuit
or leakage current
Whether the motor parameter
identification is performed
Whether there is impact
load during the operation
Whether the links between the
internal control Board and the
drive board are secured
The inverter model
is too small
Remove the peripheral fault
Perform motor parameter
identification
Remove the impact load
Secure the links
constant speed overcurrent
Check if the output loop
of the inverter has the short circuit
or leakage current
Whether the motor parameter
identification is performed
Whether there is impact
load during the operation
Whether the links between the
internal control Board and the
drive board are secured
The inverter model
is too small
Remove the peripheral fault
Perform motor parameter
identification
Remove the impact load
Secure the links
Fig. 7-4 Constant speed overcurrent (ERR04)