25
F5-05
Overcurrent stall
current value
100% ~ 200%
1%
150%
○
64
F5-06
automatic fault reset
times
0 ~ 3
1
0
○
65
F5-07
Automatic fault reset
interval
0.1s ~ 100.0s
0.1s
1.0s
○
66
F5-08
Power loss
compensation
0: Disabled
1: Enabled
1
0
67
F5-09
Inverter offload
protection
0: Disabled
1: Enabled
1
0
×
68
F5-10 Fault type
0: 0: No fault
1: Inverter unit protection (ERR01)
2: Acc overcurrent (ERR02)
3: Dec overcurrent (ERR03)
4: Overcurrent at constant speed (ERR04)
5: Acc overvoltage (ERR05)
6: Dec overvoltage (ERR06)
7: Overvoltage at constant speed (ERR07)
8: Control power supply fault (ERR08)
9: Under voltage fault (ERR09)
10: Inverter overload (ERR10)
11: Motor overload (ERR11)
12: Reserved
13: Output phase failure (ERR13)
14: Heatsink overheat (ERR14)
15: External fault (ERR15)
16: Communication fault (EER16)
17: Reserved
18: Current detection failure (ERR18)
19: Motor tuning failure (ERR19)
20: Reserved
21: EEPROM memory fault (ERR21)
22: Hardware failure (ERR22)
23: Reserved
24: Reserved
-
0
*
6
9
F5-11 Frequency at fault
-
0.1 Hz
0.0Hz
*
7
0
F5-12 Current at fault
-
0.01A
0.00A
*
7
1
F5-13 Bus voltage at fault
-
0.1V
0.0V
*
7
2
F6 Auxiliary Function