The  controller  is  equipped  with  an  adaptive  digital  filter  which  is  used  to  filter 
out  any  extraneous  pulses  on  the  PV.  Filtered  PV  Value  is  used  for  all  PV 
dependent functions. If PV signal is fluctuating due to noise, increase the filter 
time constant value.

CONTROL 

LOGIC

FOR OP1

HEAT

This parameter will appear only if selected control mode is ON-OFF. 
User can select heating logic in which OP1 will remain ON till PV < SP.
(PV increases when output is ON)

This parameter will appear only if selected control mode is ON-OFF. 
User can select cooling logic in which OP1 will remain ON till PV > SP.
(PV decreases when output is ON.)

CONTROL 

MODE 

FOR

OUTPUT1

T.P

User  can  select  between  ON-OFF  or  T.P  action  algorithm  to  be  adopted  for 
output.

OUTPUT2

FUNCTION

This parameter allow the user to select output 2 as an ‘Auxiliary’ control. 
For options refer Table 3.

This parameter allow the user to select output 2 as an ‘Alarm’ control.
For options refer Table 4.

AUX.

CONTROL

SET

POINT 2

DSBL

o

0  C

Sets  the  minimum  limit  for  set  point  adjustment.  It  can  be  set  from  minimum 
specified range of selected sensor to HSPL value.

LOWER 

SP

LIMIT

PROCESS

VALUE

OFFSET

o

0  C

Function of this parameter is to add/subtract a constant value to the measured 
PV to obtain Final PV for control applications. This parameter value needs to be 
altered for one of the following reason :
(I)  To  compensate  for  known  thermal  gradient  (ii)To  match  the  display  values 
with another recorder or indicator measuring the same PV.

J

INPUT
TYPE

This parameter value is set according to the type of sensor (Thermocouple or 
RTD Input) connected to the Controller's Input Terminals. 

HIGHER 
    SP
  LIMIT

o

400  C

Sets the maximum limit for set point adjustment. It can be set from LSPL value 
to maximum specified range of selected sensor.

(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)

 PARA
METER

DESCRIPTION

DEFAULT

DISPLAY

CONFIGURATION LIST :

 key simultaneously 

(1) To Enter in this mode, Press and hold SET & UP

for 3 sec.

(2) Press UP or DOWN key to scroll between parameter options. 

(3) Press SET key to store the current parameter & move on to the next parameter.

0

LOCK
CODE

Set this parameter to 15 (Default LOCK CODE) to access Config List.
User has a choice to set different Lock Code between 1 to 9999 via USER 
LOCK CODE in Config. List.

Fe-k(J) T/C

Cr-AL(K) T/C

Sensor Type 

Accuracy

  

o

± 1  C

o

0 ~ 1700 C

o

0 ~ 1700 C

o

-100 ~ 450 C

Resolution

Range

o

1  C

o

1  C

o

1  C

}

(R) T/C

(S) T/C

Pt-100(RTD)

Pt-100(RTD 0.1)

o

760 C

o

-99 

1300 C

o

-99.9 ~ 450.0 C

o

1  C

o

1  C

o

0.1  C

o

± 0.3  C

If Enabled, User can View & edit the Set point1  in USER list. 

If disabled, User can only View the Set Point1  but Can not edit it in USER list.

4

OIM AI-5X42 - V2.0 Page 4 of 6