The controller is equipped with an adaptive digital filter which is used to filter
out any extraneous pulses on the PV. Filtered PV Value is used for all PV
dependent functions. If PV signal is fluctuating due to noise, increase the filter
time constant value.
CONTROL
LOGIC
FOR OP1
HEAT
This parameter will appear only if selected control mode is ON-OFF.
User can select heating logic in which OP1 will remain ON till PV < SP.
(PV increases when output is ON)
This parameter will appear only if selected control mode is ON-OFF.
User can select cooling logic in which OP1 will remain ON till PV > SP.
(PV decreases when output is ON.)
CONTROL
MODE
FOR
OUTPUT1
T.P
User can select between ON-OFF or T.P action algorithm to be adopted for
output.
OUTPUT2
FUNCTION
This parameter allow the user to select output 2 as an ‘Auxiliary’ control.
For options refer Table 3.
This parameter allow the user to select output 2 as an ‘Alarm’ control.
For options refer Table 4.
AUX.
CONTROL
SET
POINT 2
DSBL
o
0 C
Sets the minimum limit for set point adjustment. It can be set from minimum
specified range of selected sensor to HSPL value.
LOWER
SP
LIMIT
PROCESS
VALUE
OFFSET
o
0 C
Function of this parameter is to add/subtract a constant value to the measured
PV to obtain Final PV for control applications. This parameter value needs to be
altered for one of the following reason :
(I) To compensate for known thermal gradient (ii)To match the display values
with another recorder or indicator measuring the same PV.
J
INPUT
TYPE
This parameter value is set according to the type of sensor (Thermocouple or
RTD Input) connected to the Controller's Input Terminals.
HIGHER
SP
LIMIT
o
400 C
Sets the maximum limit for set point adjustment. It can be set from LSPL value
to maximum specified range of selected sensor.
(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)
PARA
METER
DESCRIPTION
DEFAULT
DISPLAY
CONFIGURATION LIST :
key simultaneously
(1) To Enter in this mode, Press and hold SET & UP
for 3 sec.
(2) Press UP or DOWN key to scroll between parameter options.
(3) Press SET key to store the current parameter & move on to the next parameter.
0
LOCK
CODE
Set this parameter to 15 (Default LOCK CODE) to access Config List.
User has a choice to set different Lock Code between 1 to 9999 via USER
LOCK CODE in Config. List.
Fe-k(J) T/C
Cr-AL(K) T/C
Sensor Type
Accuracy
o
± 1 C
o
0 ~ 1700 C
o
0 ~ 1700 C
o
-100 ~ 450 C
Resolution
Range
o
1 C
o
1 C
o
1 C
}
(R) T/C
(S) T/C
Pt-100(RTD)
Pt-100(RTD 0.1)
o
0
~
760 C
o
-99
~
1300 C
o
-99.9 ~ 450.0 C
o
1 C
o
1 C
o
0.1 C
o
± 0.3 C
If Enabled, User can View & edit the Set point1 in USER list.
If disabled, User can only View the Set Point1 but Can not edit it in USER list.