(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)

 PARA

METER

RANGE

DESCRIPTION

DEFAULT

DISPLAY

User  can  change  the  SP1  value  using  UP/  DOWN  keys.  Holding  the 
key will change the value at a faster rate. Press SET key to store the 
value and move on to the next parameter.

o

0 C

LSPL ~ HSPL 

CONTROL

SET POINT

This parameter is prompted only if Output 2 is configured as...

 Either absolute auxiliary control or as an alarm (High/Low) mode.
 Either deviation auxiliary control or as a deviation alarm  mode.
  As a band alarm.(For all above Sp2 has to be enable)

(1)
(2)
(3)

LSPL ~ HSPL 

-99 to 99 °C 
   2 to 99 °C

SET

POINT2

o

0 C

CONTROL LIST : 

SET & DOWN key simultaneously  

To enter in this mode press 

for 3 sec. User can then set 

the control parameters.

MANUAL

OFFSET

o

      0  C

 This parameter will appear only if selected C.A is time proportional. 
 (For more details refer user guide.)

 PARA

METER

RANGE

DESCRIPTION

DEFAULT

DISPLAY

P. BAND

0.5 

to 

 99.9°C

This parameter will appear only if selected control action is T.P. It sets 
bandwidth  over  which  the  output  power  is  adjusted  depending  upon 
the error (SV-PV). 

o

5.0  C

DELAY 1

0

 to

500 Sec.

This parameter will appear only if selected control action is ON-OFF. 
It sets the output restart time where O/P once turned OFF will turn ON 
only  after  restart  time,  regardless  difference  between  PV  &  SP.  If  set 
to '0', O/P will be switched w/o delay. Also, Delay will be considered in 
case of every power ON.

120 Sec.

CONTROL

HYS.

o

1 to 25  C

This parameter will appear only if selected control action is ON-OFF. 
It  sets  the  dead  band  between  ON  &  OFF  switching  of  the  Output. 
Larger value of hysterisis minimize the number of ON-OFF operation 
of  the  load.  This  increases  life  of  actuators  like  contactors  but,  also 
produces large errors (between PV & SV).

2°C

This parameter will appear only if selected control mode for output2 is 
Auxiliary  control  or  an Alarm.  Value  of  this  parameter  sets  the  dead 
band between ON & OFF switching of output load.

HYS. 2 

o

1 to 25  C

o

2 C

0

 to

500 Sec.

-25

to

o

25  C 

This  parameter  will  appear  only  if  output  2  is  configured  as  an 
Auxiliary  control  output.  In  this  mode,  output  once  turned  off  will 
restart  only  after  set  time  regardless  of  the  difference  between  PV 
and SP2. If time delay is set to 0, there is no delay executed between 
output switching. 

0 Sec.

DELAY 2

CYCLE

TIME

0.5

 to 

100.0 Sec.

This parameter will appear only if selected control action is T.P. User 
can set this value based on process being controlled & type of output 
selected. For Relay O/P, cycle time should be more than 12sec & for 
SSR O/P, cycle time should  be less than 5sec.

16.0 Sec.

0

LOCK
CODE

1 ~ 9999

Set this parameter to 15 (Default LOCK CODE) to access Control 
List.
User has a choice to set different Lock Code via USER LOCK CODE 
in Config. List.

POWER UP :

At power on, following sequence will be prompted on the display for 1 sec. till it reaches to Home display mode.

In Home display mode, by pressing SET key once, user can view SP value.

MODEL

MODEL

PROGRAMMING

USER LIST : To access the user list Press & Release SET key once.

(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)

HOME

PV

VERSION

INPUT

3

OIM AI-5X42 - V2.0 Page 3 of 6