ALARM

ACK.

AUTO

Once Alarm is activated, it can be de-activated either by pressing UP key or 
when PV falls within the alarm limits.

Once Alarm is activated, it remains activated until manually acknowledged by  
UP key.

Once Alarm is activated, User has following three options to de-activate it.
When PV falls within the programmed limits, Alarm will be de-activated 
automatically.

ALARM
INHIBIT

Setting this parameter value to ‘YES’, will inhibit (suppress) Alarm activation on 
power-up  condition.  From  Power-up,  the  Alarm  system  remains  disabled  until 
PV is found with in the limits.

If Alarm activation is desired even under Power-up condition, Set this parameter 
value to ‘NO’.

NO

1) ON-OFF ACTION:

   In this mode, Output (Relay/SSR) remains ON till actual temperature reaches to Set point value.  
   On reaching SP, output turns OFF & remains OFF till actual temperature drops down (in heat logic)   
   Or raises (in cool logic) equal to hysterisis set by user. (As shown in Fig. 3.1 & 3.2).

Fig: 3.1

HEAT LOGIC/ON-OFF

TIME

0

TEMP ( C)

HYSTERISIS

SP

ON

ON

ON

AMB

O/P

OFF

OFF

Fig: 3.2

TIME

COOL LOGIC / ON OFF

O/P

O/P

0

TEMP ( C)

AMB

HYSTERISIS

ON

ON

ON

SP

OFF

OFF

USER GUIDE

:

2) TIME PROPORTIONAL ACTION:

   In this mode, ON & OFF time of Output (Relay/SSR) varies proportionally in every cycle (cycle time   
   Settable by user) depending on  the deviation of PV w.r.t. SP. This action starts/continues only             
   when PV enters or is within the band. (Fig. 3.3)

Fig: 3.3

AMB

0

TEMP ( C)

SP

OUT PUT

ON

100 %

ON

100 %

OFF

100 %

PROPORTIONAL BAND (P.BND)

SET BY USER

TIME PROPORTIONAL ACTION

ACTIVE TONE

TIME

Fig: 3.4

AMB

0

TEMP ( C)

SP

OFFSET

after offset adjustment

TIME

3) MANUAL RESET (OFFSET ADJUSTMENT): 

   In some application, after adopting-Time proportionating action system may stabilize at particular 
   temperature over a period of time which can be different than the set value. This steady state 
  (Error) offset can be eliminated by setting the value of this parameter equal and opposite to the 
   existing offset. (As shown in Fig.3.4)

NC

: Normally Close terminal of relay

NO

: Normally  Open terminal of relay   

OP1

: Output 1 

OP2

: Output 2

C.A. 

: Control Action   

CJC 

: Cold junction compensation 

CM

: Common terminal of relay  

LWC

: Lead wire (Length)  

                compensation

SP

: Set Point Value(set temp.) 

SSR

: Solid State Relay 

T.P.

: Time Proportional

T/C

: Thermocouple

ABBREVIATION :

Innovative Instruments

On

Google Play

206, New Sonal Link Service Industrial Premises Co-op Society Ltd,
Building No.2, Link Road, Malad (W), Mumbai - 400064. 
Tel: 022-66939916/17/18; 
E-mail : 

 

Website : 

  

[email protected]

www.innovativeinstruments.co.in

Mfgd  by:  Innovative  Instruments  &  Controls  LLP

i

6

OIM AI-5X42 - V2.0 Page 6 of 6

Отзывы: