AUTO TUNING MODE :

 

To enter in this mode, Press & hold SHIFT key for minimum 3 sec. 

 PARA
METER

DESCRIPTION

DEFAULT

This function will be executed only if selected control action is PID.
Auto-tuning function can be initiated by setting this parameter to ‘YES’. The decimal of 
LSB  flashes  till  Auto  Tuning  function  is  in  progress.  During  Auto-tuning,  Controller 
learns the process characteristics by itself & calculates required P, I & D values.
User can cancel or abort this feature by setting this parameter to ‘NO’.  

AUTO

TUNING

MODE

NO

DISPLAY

5

OIM AI-7X41 V2.0 Page 5 of 5

413, New Sonal Link Service Industrial Premises Co-op Society Ltd,
Building No.2, Link Road, Malad (W), Mumbai - 400064. 
Tel: 022-66939916/17/18; 
E-mail : [email protected] 
Website : www.itherm.co.in

Mfgd  by:  Innovative  Instruments  &  Controls  LLP

i

15

Default USER LOCK CODE is 15 to access Control & Configuration List.
User has a choice to set its own USER LOCK CODE between 1 to 9999, this is to 
prevent unauthorized access of Control & Configuration List. 

USER 
LOCK 
CODE

SET

POINT 1

ENABLE

If Enabled, User can View & edit the Set point 1 in USER list. 

If disabled, User can only View the Set Point 1 but Can not edit it in USER list.

AUTO

TUNE

ENABLE

If  Enabled,  this  parameter  will  be  prompted  if  user  press  Up  &  Down  keys 
Simultaneously for 3Sec. 

If Disabled, this parameter will not be prompted if user press Up & Down keys 
Simultaneously for 3Sec. 

 PARA

METER

DESCRIPTION

DEFAULT

DISPLAY

ON-OFF ACTION :

 In this mode, Output (Relay/SSR) remains ON till actual temperature reaches to the set point value. On 

reaching  SP,  Output  turns  OFF  &  remains  OFF  till  actual  temperature  drops  down  (in  Heat  logic)  or  raises  (in  Cool  logic) 
equal to hysterisis set by User. (As shown in Fig : 3.1 & 3.2)

Fig: 3.1

HEAT LOGIC / ON-OFF

TIME

0

TEMP ( C)

HYSTERISIS

SP

ON

ON

ON

AMB

O/P

OFF

OFF

Fig: 3.2

TIME

COOL LOGIC / ON OFF

O/P

O/P

0

TEMP ( C)

AMB

HYSTERISIS

ON

ON

ON

SP

OFF

OFF

USER GUIDE 

:

AUTO TUNING MODE :

 

In this mode, Controller learns the  process characteristics by itself and calculates the required P,I & 

D  values. It can be performed at any time after power ON but, it is best to start it when the process is at Ambient temperature 
in order to minimize overshoot & undershoot. Auto tuning is applied in case of : 
(1) Initial set up for a new process.
(2) Substantial change in SP from previous auto tuning value. 
(3) Control accuracy is not satisfactory. 
If the control performance by using auto-tuning is still unsatisfactory, User can apply the further adjustments of P,I & D values 
as shown below

Adjust

Proportional Band

Integral Time

Derivative Time

Slow Response
Over Shoot or Oscillations
Slow Response
Instability or Oscillation
Slow Response or Oscillation
High Over Shoot

Decrease PB
Increase  PB
Decrease  Int
Increase  Int
Decrease  Dt
Increase  Dt

Symptom

Solution