background image

i

1. DISPLAY TYPE

  : 4- Digit

 

7 segment LED (Bright White)

    STATUS LED

  : OP 1 : Main Control Output

2. INPUT

     Sensor input

: TC:J,K,R,S,N,T,B & RTD: Pt-100

     Range

: Refer below table.

     

     

     Sampling Time                     : 125 msec.

     Resolution

  : 1°C/0.1°C(Only for RTD)

     CJC for TC

  : Built in automatic

     LWC for Pt-100

  : Built in upto 18E max.

     Digital Filter                          : 1 to 10 Sec.

3. RELAY OUTPUT

     Contact type

: N/O, CM, N/C

     Contact Rating

  : 5A @ 250VAC or 30 VDC

     Life expectancy

  : > 5,00,000 operations

     Isolation

  : Inherent

4. SSR DRIVE OUTPUT

     Drive Capacity

  : 12V @ 30mA.

     Isolation

  : Non-Isolated.

5. FUNCTION

 

     Output 1

  : Main Control output

     Control Action                      : ON-OFF/PID (Select)

     Control Mode                        : Heat/Cool (Select)

   

6. ENVIRONMENTAL

     Operating Range

  : 0 ~50°C, 5~90% Rh

     Storage Humidity

  : 95% Rh (Non-condensing)

7. POWER SUPPLY

     Supply Voltage

  : 90~270VAC, 50/60Hz.

     Consumption

: 4W Maximum.

8. PHYSICAL

     Housing

  : ABS Plastic

SPECIFICATIONS : -

      SAFETY INSTRUCTION : -

      This controller is meant for temperature control applications. 
      It is important to read the manual prior to installing or 
      commissioning of controller. All safety related instruction 
      appearing in this manual must be followed to ensure safety 
      of the operating personnel as well as the instrument.

      GENERAL : -

v

The controller must be configured correctly for intended 

      operation. Incorrect configuration could result in damage 
      to the equipment or the process under control or it may 
      lead personnel injury.

v

The controller is generally part of control panel and in 

      such a case the terminals should not remain accessible 
      to the user after installation.

      MECHANICAL : -

v

The Controller in its installed state must not come in close 

      proximity to any corrosive/combustible gases, caustic 
      vapors, oils, steam or any other process by-products.

v

The Controller in its installed state should not be exposed 

      to carbon dust,  salt  air, direct sunlight or radiant heat.

v

Ambient temperature and relative humidity surrounding 

      the controller must not exceed the maximum specified 
      limit  for proper operation of the controller.

v

The controller in its installed state must be protected 

      against excessive electrostatic or electromagnetic 
      interferences. Ventilation slits provided on the chassis of 
      the instrument are meant for thermal dissipation hence 
      should not be obstructed in the panel.

      ELECTRICAL : -

v

The controller must be wired as per wiring diagram & it 

      must comply with local electrical regulation.

v

Care must be taken not to connect AC supplies to low 

      voltage sensor input.

v

Circuit breaker or mains s/w with fuse (275V/1A) must be 

      installed between power supply and supply terminals to 
      protect the controller from any possible damage due to 
      high voltage surges of extended  duration.

v

Circuit  breaker  and  appropriate  fuses  must be used for 

      driving high voltage loads to protect the controller from 
      any possible damage due to short circuit on loads.

v

To minimize pickup of electrical noise, the wiring for low 

      voltage DC and sensor input must be routed away from 
      high current power cables. Where it is impractical to do 
      this, use shielded ground at both ends.

v

The controller should not be wired to a 3-Phase supply 

      with unearthed star connection. Under fault condition 
      such supply could rise above 264 VAC which will damage 
      the controller.

v

The Electrical noise generated by switching inductive 

      loads might create momentary Fluctuation in display, 
      alarm latch up, data loss or permanent damage to the 
      instrument. To reduce this use snubber circuit across the 
      load.

It is essential to install a over Temp. Protection device to 

      avoid any failure of heating system. Apart from spoiling 
      the product, this could damage the process being 
      controlled.

( Models : AI 7441 / 7841 / 7741 / 7941 )

USER’S  OPERATING  MANUAL  FOR  PID  DIGITAL  TEMPERATURE  CONTROLLER

AI - 7441

(48 X 48)

1

OIM AI-7X41 V2.0 Page 1 of 5

AI - 7841

(48 X 96)

AI - 7741

(72 X 72)

AI - 7941

(96 X 96)

Model no.

Display height

AI-7441 AI-7841 AI-7741

0.36”

AI-7941

0.56”

0.56”

0.56”

Fe-k(J) T/C

Cr-AL(K) T/C

Sensor Type 

Accuracy

  

o

± 1  C

o

0 ~ 1700 C

o

0 ~ 1700 C

o

0 ~ 1800 C

o

-100 ~ 450 C

Resolution

Range

o

1  C

o

1  C

o

1  C

}

(R) T/C

(S) T/C

TC - N

TC - T

TC - B

Pt-100(RTD)

Pt-100(RTD 0.1)

o

760 C

o

-99 

1300 C

o

-99 

1300 C

o

-99 

400 C

o

-99.9 ~ 450.0 C

o

1  C

o

1  C

o

1  C

o

1  C

o

1  C

o

0.1  C

o

± 0.3  C

Model no.

Weight (gms.)

AI-7441

130

200

200

AI-7841 AI-7741

240

AI-7941

Отзывы: