CONFIGURATION LIST :

 (1) 

 key simultaneously 

To enter in this mode, press and hold SET & UP

for 3 sec. 

(2) Press UP or DOWN key to scroll between parameter options. 
(3) Press SET key to store the current parameter & move on to the next parameter.

(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)

4

OIM AI-7X41 V2.0 Page 4 of 5

PROCESS 

VALUE

OFFSET

o

0  C

Function  of  this  parameter  is  to  add/subtract  a  constant  value  to  the  measured  PV  to 
obtain  Final  PV  for  control  applications.  This  parameter  value  needs  to  be  be  altered  for 
one of the following reason : -
(i) To compensate for known thermal gradient 
(ii)To match the display values with another recorder or indicator measuring the same PV.

HIGHER 
    SP
  LIMIT

o

400  C

Sets  the  maximum  limit  for  set  point  adjustment.  It  can  be  set  from  LSPL  value  to 
maximum specified range of selected sensor.

LOWER 

SP 

LIMIT

o

0  C

Sets  the  minimum  limit  for  set  point  adjustment.  It  can  be  set  from  minimum  specified 
range of selected sensor to HSPL value.

CONTROL 

LOGIC

HEAT

This parameter will be prompted only if selected control mode is ON-OFF. 
User can select HEAT logic in which OP1 will remain ON till PV < SP.
(PV increases when output is ON.)

This parameter will be prompted only if selected control mode is ON-OFF. 
User can select cooling logic in which OP1 will remain ON till PV > SP.
(PV decreases when output is ON.)

CONTROL 

MODE

PID

User can select between PID or ON-OFF action algorithm to be adopted for output.

INPUT

FILTER

4

Controller  is  equipped  with  an  adaptive  digital  filter  which  is  used  to  filter  out  any 
extraneous  pulses  on  the  PV.  Filtered  PV  Value  is  used  for  all  PV  dependent  functions.  If 
PV signal is fluctuating due to noise, increase the filter time constant value.

TC - J

INPUT

TYPE

This parameter value is set according to the type of sensor (Thermocouple or 
RTD input) connected to the controller's input terminals. 

o

0.3  C

  

±

Fe-k(J) T/C

Cr-AL(K) T/C

Pt-100(RTD)

Sensor Type 

Accuracy

o

760 C

o

-99 

1300 C

o

-99 

1300 C

o

-99 

400 C

o

1800 C

o

-100 

450 C

Resolution

Range

o

1  C

o

1  C

o

1  C

}

(R) T/C

(S) T/C

TC - N

TC - T

TC - B

Pt-100(RTD 0.1)

o

-

100.0 ~ 450.0 C

o

0 ~ 1700 C

o

0 ~ 1700 C

o

1  C

o

1  C

o

1  C

o

1  C

o

0.1  C

o

1  C

  

±

o

C

 PARA
METER

DESCRIPTION

DEFAULT

DISPLAY

0

LOCK 
CODE

Set this parameter to 15 (Default LOCK CODE) to access Config. List.
User has a choice to set different Lock Code between 1 to 9999 via USER LOCK CODE in 
Config. List.

OVERSHOOT

CONTROL 

POINT

DISABLE

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID.  Setting  this  parameter  on 
higher side will slows down the rate of rise of PV to minimize overshoot (this may cause delay to 
reach  SP).  Disabling  or  Setting  this  parametr  on  lower  side  will  increase  the  rate  of  rise  of  PV 
(which may cause overshoot). Disable this option if delay is not required to reach SP.
(This may cause overshoot w.r.t. SP)

OUTPUT                 

TYPE

RELAY

User  has  to  set  this  parameter  very  carefully  in  accordance  with  the  output  used.               
(Separate terminal for RELAY & SSR : - Refer  electrical installation )
Select Relay if LOAD is connected via contactor. Whenever user selects Relay, Cycle time will 
automatically set to 16 sec. User can modify cycle time via Control List.

Select  SSR  if  LOAD  is  connected  via    SSR  (DC  voltage  pulses).  Whenever  user  selects   
SSR , Cycle time will automatically set to 1sec. User can modify cycle time via Control List.