User can change SP value using UP/ DOWN keys. Holding the key, will change
the value at a faster rate. Press SET key to store the value & move on to the
next parameter.
o
0 C
LSPL ~ HSPL
Control
Set Point
PROGRAMMING :
POWER UP :
At power on, following sequence will be prompted on the display for 1 sec. till it reaches to Home display mode.
USER LIST : To access the user list Press & Release SET key once.
(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options).
(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)
PARA
METER
RANGE
DESCRIPTION
DEFAULT
DISPLAY
PARA
METER
RANGE
DESCRIPTION
DEFAULT
DISPLAY
MODEL
VERSION
HOME
INPUT
PV
PRORTIONAL
BAND
INTEGRAL
TIME
DERIVATIVE
TIME
CYCLE
TIME
CONTROL
HYS.
0.5
to
99.9°C
o
1 to 25 C
0
to
9999 Sec.
0
to
300 Sec.
0.5
to
100.0 Sec.
50 %
to
100 %
This parameter will be prompted only if selected control action is PID. It sets
bandwidth over which the output power is adjusted depending upon the error
(SV-PV). The value of this parameter is automatically set by Auto tune function.
This parameter will be prompted only if selected control action is PID. It defines
how strongly the Controller will react to the rate of change of PV. Value of this
parameter is automatically set by Auto Tune function. If set to ‘0’, this function
will be disabled.
This parameter will be prompted only if selected control action is PID. User can
set this value based on process being controlled & type of Output being
selected. For Relay O/P, cycle time should be more than 12sec & for SSR O/P,
cycle time should be less than 5 Sec.
This parameter will be prompted only if selected control action is ON-OFF. It
sets the dead band between ON & OFF switching of the Output. Larger value of
hysterisis minimize the number of ON-OFF operation of load. This increases life
of actuators like contactors but also produces large errors (between PV & SV).
This parameter will be prompted only if selected control action is PID. It sets
the time taken by PID algorithm to remove steady state error. Value of this
parameter is automatically set by Auto Tune function. If set to ‘0’, this function
will be disabled.
o
5.0 C
240
60
16.0 Sec.
100 %.
100 %.
2°C
DELAY
0
to
500 Sec.
This parameter will be prompted only if selected control action is ON-OFF. It
sets the output restart time where O/P once turned OFF will turn ON only after
restart time, regardless difference between PV & SP in Heat or Cool mode. If set
to '0', O/P will be switched without delay. Also, Delay will be applicable at every
power ON.
0 Sec.
0
LOCK
CODE
1 ~ 9999
Set this parameter to 15 (Default LOCK CODE) to access Control List.
User has a choice to set different Lock Code via USER LOCK CODE in Config.
List.
CONTROL LIST :
SET & DOWN key simultaneously
To enter in this mode press
for 3 sec. User can set the control parameters.
OUTPUT
POWER
LIMIT
TUNE
OFFSET
0.0 %
TO
100.0 %
This parameter will be prompted only if selected control action is PID. This
parameter will decide the maximum output power in % applied to the load
This parameter will be promted only if selected control action is PID.This
parameter allows the user to carry out Auto Tuning function below the set
point. (If tune offset is set to 50 %, tuning will be carried out at 50 % of the set
point and If set to 100 %, tuning will be carried out at 100 % of the set point.)
OUTPUT
OFF
This parameter will be prompted only if selected control action is PID.
With this parameter O/P will be Completely OFF after the Set Point +
Offset Value. If Disable, O/P will act Depending upon the PID Value
after Set Point achieved.
Disable
1 to 10
3