i

User can change SP value using UP/ DOWN keys. Holding the key,  will change 
the  value  at  a  faster  rate.  Press  SET  key  to  store  the  value  &  move  on  to  the 
next parameter.

o

0 C

LSPL ~ HSPL 

Control

Set Point

PROGRAMMING :

POWER UP :

At power on, following sequence will be prompted on the display for 1 sec. till it reaches to Home display mode.

USER LIST : To access the user list Press & Release SET key once.

(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options).

(All following selected parameter’s code shown in shaded will be displayed for 1 sec. followed by their values / options)

 PARA

METER

RANGE

DESCRIPTION

DEFAULT

DISPLAY

 PARA

METER

RANGE

DESCRIPTION

DEFAULT

DISPLAY

MODEL

VERSION

HOME

INPUT

PV

PRORTIONAL

BAND

INTEGRAL

TIME

DERIVATIVE

TIME

CYCLE

TIME

CONTROL

HYS.

0.5 

to 

99.9°C

o

1 to 25  C

to 

9999 Sec.

to 

300 Sec.

0.5

 to 

100.0 Sec.

50 %

 to 

100 %

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID.  It  sets 
bandwidth  over  which  the  output  power  is  adjusted  depending  upon  the  error 
(SV-PV). The value of this parameter is automatically set by Auto tune function.

This parameter will be prompted only if selected control action is PID. It defines 
how strongly the Controller will react to the rate of change of PV. Value of this 
parameter is automatically set by Auto Tune function. If set to ‘0’, this function 
will be disabled.

This parameter will be prompted only if selected control action is PID. User can 
set  this  value  based  on  process  being  controlled  &  type  of  Output  being 
selected.  For  Relay  O/P,  cycle  time  should  be  more  than  12sec  &  for  SSR  O/P, 
cycle time should  be less than 5 Sec.

This  parameter  will  be  prompted  only  if  selected  control  action  is  ON-OFF.  It 
sets the dead band between ON & OFF switching of the Output. Larger value of 
hysterisis minimize the number of ON-OFF operation of load. This increases life 
of actuators like contactors but also produces large errors (between PV & SV).

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID.  It  sets 
the  time  taken  by  PID  algorithm  to  remove  steady  state  error.  Value  of  this 
parameter is automatically set by Auto Tune function. If set to ‘0’, this function 
will be disabled.

o

5.0 C

  240

   60

16.0 Sec.

100 %.

100 %.

2°C

DELAY 

0

 to

500 Sec.

This  parameter  will  be  prompted  only  if  selected  control  action  is  ON-OFF.  It 
sets the output restart time where O/P once turned OFF will turn ON only after 
restart time, regardless difference between PV & SP in Heat or Cool mode. If set 
to '0', O/P will be switched without delay. Also, Delay will be applicable at every 
power ON.

0 Sec.

0

LOCK
CODE

1 ~ 9999

Set this parameter to 15 (Default LOCK CODE) to access Control List.
User has a choice to set different Lock Code via USER LOCK CODE in Config. 
List.

CONTROL LIST :

 

 SET & DOWN key simultaneously  

To enter in this mode press 

for 3 sec. User can set the control parameters.

OUTPUT
 POWER

LIMIT

TUNE 

OFFSET

0.0 %

TO

100.0 %

This  parameter  will  be  prompted  only  if  selected  control  action  is  PID.  This 
parameter will decide the maximum output power in % applied to the load

This parameter will be promted only if selected control action is PID.This 
parameter  allows the user to carry out Auto Tuning function below the set 
point. (If tune offset is set to 50 %, tuning will be carried out at 50 % of the set 
point and If set to 100 %, tuning will be carried out at 100 % of the set point.)

OUTPUT

OFF

This parameter will be prompted only if selected control action is PID. 
With this parameter  O/P will be Completely OFF after the Set Point + 
Offset Value. If Disable, O/P will act Depending upon the PID Value 
after Set Point achieved.

Disable

1  to 10 

3

OIM AI-7X41 V2.0 Page 3 of 5