For other models, when the compressor is
running, the indoor fan will run at setting fan
speed. When the setting temp.is reached, the
indoor fan will run at lowest fan speed.
Auto fan running rules:
For NIN516C2V31,
a
b
c
d
5.0
4.0
2.5
1.0
6.0
T1-Ts
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
8.4.3 Drying mode
8.4.3.1 Indoor fan speed is fixed at breeze
and can’t be changed. The louver angle is the
same as in cooling mode.
8.4.3.2 Compressor running rules
2.0
1.5
1.0
F3
F2
F1
F1
2.5
0.5
0.0
8.4.3.3 Low indoor room temperature protection
In drying mode, if room temperature is lower
than 10
℃
, the compressor will stop and not
resume until room temperature exceeds 12
℃
.
8.4.3.4 Evaporator anti-freezing protection,
condenser high temperature protection and
outdoor unit frequency limit are active and the
same as that in cooling mode.
8.4.3.5 The outdoor fan operates the same as
in cooling mode.
8.4.4 Forced operation function
8.4.4.1 Enter forced operation function:
When the machine is off, pressing the touch
button will carry the machine to forced auto
mode. If pressing the button once again within
5 seconds, the machine will turn into forced
cooling mode.
In forced auto, forced cooling or any other
operation mode, pressing touch button will turn
off the machine.
8.4.4.2 In forced operation mode, all general
protections and remote control are available.
8.4.4.3 Operation rules:
Forced cooling mode:
The compressor runs at F2 frequency and
indoor fan runs as breeze. After running for 30
minutes. the machine will turn to auto mode as
24
℃
setting temperature.
Forced auto mode:
The action of forced auto mode is the same as
normal auto mode with 24
℃
setting
temperature.
8.4.5 Timer function
8.4.5.1 Timing range is 24 hours.
8.4.5.2 Timer on. The machine will turn on
automatically when reaching the setting time.
8.4.5.3 Timer off. The machine will turn off
automatically when reaching the setting time.
8.4.5.4 Timer on/off. The machine will turn on
automatically when reaching the setting “on”
time, and then turn off automatically when
reaching the setting “off” time.
8.4.5.5 Timer off/on. The machine will turn off
automatically when reaching the setting “off”
time, and then turn on automatically when
reaching the setting “on” time.
8.4.5.6 The timer function will not change the
AC current operation mode. Suppose AC is off
now, it will not start up firstly after setting the
31
Innovair Corporation
Nexxos Inverter
Содержание NIN1225C2V31
Страница 6: ...2 2 Part names of Indoor Outdoor units 4 Innovair Corporation Nexxos Inverter ...
Страница 13: ...5 Wiring Diagram 5 1 Indoor Unit NIN516C2V31 ID 11 Innovair Corporation Nexxos Inverter ...
Страница 14: ...NIN522C2V31 ID 12 Innovair Corporation Nexxos Inverter ...
Страница 15: ...NIN1225C2V31 ID 13 Innovair Corporation Nexxos Inverter ...
Страница 16: ...5 2 Outdoor Unit NIN516C2V31 OD 14 Innovair Corporation Nexxos Inverter ...
Страница 17: ...NIN522C2V31 OD 15 Innovair Corporation Nexxos Inverter ...
Страница 18: ...NIN1225C2V31 OD 16 Innovair Corporation Nexxos Inverter ...
Страница 19: ...For NIN516C2V31 OD 17 Innovair Corporation Nexxos Inverter ...
Страница 20: ...For NIN522C2V31 OD 18 Innovair Corporation Nexxos Inverter ...
Страница 21: ...For NIN1225C2V31 OD 19 Innovair Corporation Nexxos Inverter ...
Страница 39: ...9 2 Outdoor unit error display For NIN516C2V31 OD 37 Innovair Corporation Nexxos Inverter ...
Страница 49: ...P U P V 47 Innovair Corporation Nexxos Inverter ...
Страница 50: ...P W P N 48 Innovair Corporation Nexxos Inverter ...
Страница 78: ...76 Innovair Corporation Nexxos Inverter ...