Remark:
Use a multimeter to test the DC
voltage between L2 port and S port of
outdoor unit. The red pin of
multimeter connects with L2 port
while the black pin is for S port.
When AC is normal running, the
voltage will move alternately between
-50V to 50V.
If the outdoor unit has malfunction,
the voltage will move alternately with
positive value.
While if the indoor unit has
malfunction, the voltage will be a
certain value.
Remark:
Use a multimeter to test the
resistance of the reactor which does
not connect with capacitor.
The normal value should be around
zero ohm. Otherwise, the reactor
must have malfunction and need to
be replaced.
41
Innovair Corporation
Nexxos Inverter
Содержание NIN1225C2V31
Страница 6: ...2 2 Part names of Indoor Outdoor units 4 Innovair Corporation Nexxos Inverter ...
Страница 13: ...5 Wiring Diagram 5 1 Indoor Unit NIN516C2V31 ID 11 Innovair Corporation Nexxos Inverter ...
Страница 14: ...NIN522C2V31 ID 12 Innovair Corporation Nexxos Inverter ...
Страница 15: ...NIN1225C2V31 ID 13 Innovair Corporation Nexxos Inverter ...
Страница 16: ...5 2 Outdoor Unit NIN516C2V31 OD 14 Innovair Corporation Nexxos Inverter ...
Страница 17: ...NIN522C2V31 OD 15 Innovair Corporation Nexxos Inverter ...
Страница 18: ...NIN1225C2V31 OD 16 Innovair Corporation Nexxos Inverter ...
Страница 19: ...For NIN516C2V31 OD 17 Innovair Corporation Nexxos Inverter ...
Страница 20: ...For NIN522C2V31 OD 18 Innovair Corporation Nexxos Inverter ...
Страница 21: ...For NIN1225C2V31 OD 19 Innovair Corporation Nexxos Inverter ...
Страница 39: ...9 2 Outdoor unit error display For NIN516C2V31 OD 37 Innovair Corporation Nexxos Inverter ...
Страница 49: ...P U P V 47 Innovair Corporation Nexxos Inverter ...
Страница 50: ...P W P N 48 Innovair Corporation Nexxos Inverter ...
Страница 78: ...76 Innovair Corporation Nexxos Inverter ...