9.3.5 Open circuit or short circuit of temperature sensor diagnosis and solution(E5)
Error Code
E5
Malfunction decision
conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V,
the LED will display the failure.
Supposed causes
●
Wiring mistake
●
Sensor faulty
Trouble shooting:
Check the connections
between temperature
sensor and main PCB.
Are the connections
good?
Correct the connections.
No
Yes
Yes
Replace indoor or
outdoor main PCB.
Replace the sensor and
check if the problem happen
again?
Check the resistance value
of the sensor via
table1(p64)and table
2(p65), is it normal?
No
45
Innovair Corporation
Nexxos Inverter
Содержание NIN1225C2V31
Страница 6: ...2 2 Part names of Indoor Outdoor units 4 Innovair Corporation Nexxos Inverter ...
Страница 13: ...5 Wiring Diagram 5 1 Indoor Unit NIN516C2V31 ID 11 Innovair Corporation Nexxos Inverter ...
Страница 14: ...NIN522C2V31 ID 12 Innovair Corporation Nexxos Inverter ...
Страница 15: ...NIN1225C2V31 ID 13 Innovair Corporation Nexxos Inverter ...
Страница 16: ...5 2 Outdoor Unit NIN516C2V31 OD 14 Innovair Corporation Nexxos Inverter ...
Страница 17: ...NIN522C2V31 OD 15 Innovair Corporation Nexxos Inverter ...
Страница 18: ...NIN1225C2V31 OD 16 Innovair Corporation Nexxos Inverter ...
Страница 19: ...For NIN516C2V31 OD 17 Innovair Corporation Nexxos Inverter ...
Страница 20: ...For NIN522C2V31 OD 18 Innovair Corporation Nexxos Inverter ...
Страница 21: ...For NIN1225C2V31 OD 19 Innovair Corporation Nexxos Inverter ...
Страница 39: ...9 2 Outdoor unit error display For NIN516C2V31 OD 37 Innovair Corporation Nexxos Inverter ...
Страница 49: ...P U P V 47 Innovair Corporation Nexxos Inverter ...
Страница 50: ...P W P N 48 Innovair Corporation Nexxos Inverter ...
Страница 78: ...76 Innovair Corporation Nexxos Inverter ...