Diagnosis and Solution
E1
EEPROM parameter error diagnosis and solution
If the EEPROM chip
is welded on main
PCB, replace the
main PCB directly.
Otherwise, check
whether the
EEPROM chip
plugged in main PCB
well?
Yes
No
Yes
Correct the connection.
Replace the indoor main
PCB.
Shut off the power supply and
turn it on 5 seconds later. Is it
still displaying the error code?
EEPROM: a read-only memory whose contents can be erased and reprogrammed using a pulsed voltage.
E2
Zero crossing signal detection error diagnosis and solution
Check if the connections and
power supply is normal?
Correct the connections. Turn on the
unit when the power supply is good.
No
Yes
Indoor main PCB is
defective. Replace indoor
main PCB.