24
5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
6). Set the 3-way valve to the closed position immediately
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
Disconnect the charge set, and tighten the 2-way and 3-way valve’s stem nuts.
Use a torque wrench to tighten the 3-way valves service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
2. Air purging by the refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve
Leave the valve on the charging cylinder closed.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on
the 2-way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Содержание BIN312C2V31
Страница 1: ...CSI 1206 A SERVICE MANUAL BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 AIR CONDITIONER ...
Страница 12: ...10 Model R mm L mm H mm Dimension of installation hole mm BIN625C2V31 106 5 70 45 65 ...
Страница 16: ...14 5 Wiring Diagram 5 1 Indoor Unit BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 ...
Страница 17: ...15 5 2 Outdoor Unit BIN312C2V31 BIN520C2V31 ...
Страница 18: ...16 BIN625C2V31 BIN414C2V31 202037391056 ...
Страница 29: ...27 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...
Страница 40: ...38 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution ...
Страница 41: ...39 9 2 2 Indoor outdoor units communication protection diagnosis and solution ...
Страница 42: ...40 9 2 3 Zero crossing signal diagnosis and solution ...
Страница 43: ...41 9 2 4 Indoor fan speed has been out of control diagnosis and solution ...
Страница 44: ...42 9 2 5 Open or short circuit of temperature sensor diagnosis and solution ...
Страница 45: ...43 9 2 6 IPM malfunction or IGBT over strong current protection diagnosis and solution ...
Страница 46: ...44 9 2 7 Over voltage or too low voltage protection diagnosis and solution ...