19
6.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested
and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles
come out, the pipes have leakage.
1. Air purging with vacuum pump
1. Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the
2-way and
3-way valves are set to the closed position.
2. Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port..
3. Connect the charge hose of handle hi connection to the vacuum pump.
4. Fully open the handle Lo of the manifold valve.
5. Operate the vacuum pump to evacuate.
6. Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
(Indoor unit)
(Liquid side)
(Gas side)
Vacuum
pump
Vacuum
pump
Lo
Hi
Handle Hi
Two-way valve
Close
Manifold valve
Compound meter
Pressure
gauge
-0
.1Mp
a
Handle Lo
Charge hose
Charge hose
(Outdoor unit)
Close
Three-way valve
Содержание BIN312C2V31
Страница 1: ...CSI 1206 A SERVICE MANUAL BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 AIR CONDITIONER ...
Страница 12: ...10 Model R mm L mm H mm Dimension of installation hole mm BIN625C2V31 106 5 70 45 65 ...
Страница 16: ...14 5 Wiring Diagram 5 1 Indoor Unit BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 ...
Страница 17: ...15 5 2 Outdoor Unit BIN312C2V31 BIN520C2V31 ...
Страница 18: ...16 BIN625C2V31 BIN414C2V31 202037391056 ...
Страница 29: ...27 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...
Страница 40: ...38 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution ...
Страница 41: ...39 9 2 2 Indoor outdoor units communication protection diagnosis and solution ...
Страница 42: ...40 9 2 3 Zero crossing signal diagnosis and solution ...
Страница 43: ...41 9 2 4 Indoor fan speed has been out of control diagnosis and solution ...
Страница 44: ...42 9 2 5 Open or short circuit of temperature sensor diagnosis and solution ...
Страница 45: ...43 9 2 6 IPM malfunction or IGBT over strong current protection diagnosis and solution ...
Страница 46: ...44 9 2 7 Over voltage or too low voltage protection diagnosis and solution ...