23
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low
side), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air
conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
6.6 Re-installation while the indoor unit need to be repaired
1. Collecting the refrigerant into the outdoor unit
Procedure
1). Confirm that both the 2-way and 3-way valves are set to the opened position
Remove the valve stem caps and confirm that the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose.
Open the handle Lo valve of the manifold valve
slightly to purge air from the charge hose for 5 seconds
and then close it quickly.
4). Set the 2-way valve to the close position.
Содержание BIN312C2V31
Страница 1: ...CSI 1206 A SERVICE MANUAL BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 AIR CONDITIONER ...
Страница 12: ...10 Model R mm L mm H mm Dimension of installation hole mm BIN625C2V31 106 5 70 45 65 ...
Страница 16: ...14 5 Wiring Diagram 5 1 Indoor Unit BIN312C2V31 BIN414C2V31 BIN520C2V31 BIN625C2V31 ...
Страница 17: ...15 5 2 Outdoor Unit BIN312C2V31 BIN520C2V31 ...
Страница 18: ...16 BIN625C2V31 BIN414C2V31 202037391056 ...
Страница 29: ...27 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...
Страница 40: ...38 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution ...
Страница 41: ...39 9 2 2 Indoor outdoor units communication protection diagnosis and solution ...
Страница 42: ...40 9 2 3 Zero crossing signal diagnosis and solution ...
Страница 43: ...41 9 2 4 Indoor fan speed has been out of control diagnosis and solution ...
Страница 44: ...42 9 2 5 Open or short circuit of temperature sensor diagnosis and solution ...
Страница 45: ...43 9 2 6 IPM malfunction or IGBT over strong current protection diagnosis and solution ...
Страница 46: ...44 9 2 7 Over voltage or too low voltage protection diagnosis and solution ...