To install the condensate drain, comply with the following
standards:
•
give a slope of at least 2% to the exhaust pipe;
•
provide for the possibility of disconnecting the drain
hose for any maintenance (especially in the case of
ceiling installation);
•
make sure that the discharge end of the pipe is at least
below the water level of the siphon;
•
make sure that the siphon is always full of water.
In horizontal positioning the drain is 18 mm in diameter;
In vertical positioning, the drain is 20 mm in diameter;
Horizontal installation drain
Vertical installation drain
3
AREAULIC CONNECTIONS
3.1
AREAULIC CONNECTIONS
The unit is equipped with circular male connections of different diameters for the renewal and recirculation air part;
On the other hand, a rectangular outlet is provided for the part of the ambient inlet air;
For the correct connection of the air ducts, refer to the following diagram and the stickers placed on the unit.
Horizontal installation
The configurations for the aeraulic flows and
connections are indicated on the side:
A-
Air delivery
B-
Air intake