Page 35
Omni Installation Instructions
© Mass Electronics Pty Ltd 2017
Chapter 3 – Electrical Installation
Current Loop Output
Range
0mA to 20mA
Resolution
12bit @ 4096 steps
Maximum Output Voltage
9VDC @ 20mA
Accuracy
±1.5% of reading ±4LSB @ 20°C (68°F)
Drift
±200ppm/°C
Digital Duty Cycle Output
Frequency Range
60mHz to 976Hz
Duty Cycle Resolution
14bit (16383 steps)
Duty Cycle Range
0 to 100%
Switch Modes
As per Digital Output specifications
Digital Pulse Output
Pulse Width Range
10µs to 268s
Pulse Resolution
16bit (65535 steps)
Switch Modes
As per Digital Output specifications
Digital Output
Switch Modes
Toggle Switching (Auto)
On = 12VDC
Off = 0V
High Side Switching
On = 12VDC
Off = Open
Low Side Switching
On = 0V
Off = Open
Switch Current
Refer to Note
Protection
Inrush and short circuit protected
Response Time: 64µs
For High Side and Toggle Switching modes, maximum available power is limited (45mA).
For Low Side Switching, each channel can switch 200mA.
Caution must be used when using Low Side Switching. For more information, contact your
Innotech representative.
Voltage Output
Range
0V to 10VDC
Resolution
12bit @ 4096 steps
Impedance
~80Ω
Maximum Current
10mA
Accuracy
±1.5% of reading ±4LSB @ 20°C (68°F) &
R
load
>10kΩ
Drift
±200ppm/°C
Programmable Point Specifications (Continued)
Содержание Omni C14
Страница 1: ...Omni INSTALLATION INSTRUCTIONS...
Страница 11: ...Omni INSTALLATION INSTRUCTIONS Preliminary Information 1...
Страница 17: ...Omni INSTALLATION INSTRUCTIONS Mechanical Installation 2...
Страница 31: ...Omni INSTALLATION INSTRUCTIONS Electrical Installation 3...
Страница 53: ...Omni INSTALLATION INSTRUCTIONS Networking 4...
Страница 74: ...Omni INSTALLATION INSTRUCTIONS Commissioning 5...