The above table is the difference between the continuous timer mode and the
target timer mode of the thermostat, which is represented by the curve image
as follows:
0
5
10
15
20
25
30
35
40
0 1 2 3 4 5 6 7 8 9 101112131415161718192021222324252627
2829303132333435363738394041
er
ut
ar
ep
me
T
Time [min]
Timer mode CS
Continuous vs. Target mode
CS = C
CS = T
From the graph, we can see that when TR=1, the continuous
timer mode (the blue line),the stage control time H01~H03 is
continuous time, 0...10,11...17,18...29, total is 29 minutes;
When TR=2, the target timer mode (the red line),the stage
control time H01~H03 is only started when the current
temperature reaches the setting temperature of the current
stage, such as 5...14, 19...25, 32...35, and total is 39 minutes.
4.6.3 UT
is a time unit setting parameter, and the user can set
the time unit to days, hours or minutes as required
;
4.6.4 STT
is the setting stages of the time – temperature
period. Users can set different time periods to control different
temperature according to their needs. At most 12 time periods
can be set to control 12 different temperature.
4.6.5 SST
is the beginning stage of time - temperature
period. Users can select which stage to start control
according to their own requirements.
4.6.6 S01~S12
are temperature setting parameters. When
TR=1 or 2, the setting value of ST1~ST12 will replace the TS
value as the condition parameter of temperature control;
4.6.7 H01~H12
are duration parameters, and the current
Output(WORK1/WORK2) Instruction
WORK1:
The P1 heating/cooling output
WORK2:
The P2 heating/cooling output
Indicator LED:
●
Red LED is on WORK1 output is on.
●
Red LED is blinking WORK1 output is performing the
function of compressor delay.
●
Green LED is on WORK2 output is on.
●
Green LED is blinking WORK2 output is performing the
function of compressor delay.
●
Yellow LED is on The controller is in the setting mode.
Button Instruction
Please read the detail on
2.Button Operation Instructions
below
Probe interface
Two temperature probes can be insert into P1 and P2 interface.
Temperature probe
●
If the controller display Er, you may get a false temperature
probe, please try harder to insert the probe and rotate it to make
good contact. If the problem is still persists, it is likely the
internal probe wire has been damaged by the moisture or heat
temperature.
●
The probe and cable cannot be touched by the flame.
●
Do not exceed the probe temperature range to avoid
damaging.
2 Button Operation Instructions
2.1 Restore Default Settings
Press and hold the “ " button to power on, the buzzer will
make a short call, indicating that all parameters of the user's
temperature and humidity probe function return to the default
setting value.
2.2 “ ” and “ ”Button Function in Normal Operation
Mode
Press the “ ", PV shows the current temperature setting
value , SV shows current humidification value; press “ ", PV
shows current temperature value, SV the current humidification
setting value , and It will be back to the normal display if there is
no operation for 3 seconds orpressing the "
SET
" button.
2.3 “SET” Button Function in Normal Operation Mode
Short press the “
SET
” button to enter the quick setting
temperature and humidity value mode. PV shows the current
temperature setting value and flashes, and short press “ ” or
“ ” button to increase or decrease the setting value, long
press “ ” or “ ”button to quickly increase or decrease the
setting value, Short press the “
SET
” button again
,
SV shows
the current humidity setting value and flashes, and short press
“ ” or “ ” button to increase or decrease the setting value,
long press “ ” or “ ”button to quickly increase or decrease
the setting value and lastly press the "
SET
" button again to
confirm and exit. If there is no operation, it will automatically
exit after 10 seconds and save the setting value.
2.4 Button Function in Setting Mode
When the controller is working normally, press the “
SET
” button
for 2 seconds to enter the setting mode
,
the PV shows the first
menu code“
”, SV shows the corresponding setting value.
Press “
SET
” button to scroll down the menu item and save the
parameters of the previous menu item. Press“ ” or
“ ”button to change the current setting value. Selected T to
enter the temperature parameter modification mode; selected H
to enter the humidity parameter modification mode. If in the
setting state, there is no operation within 30 seconds or long
press "
SET
" button for 2 seconds, it will exit and save the
setting state and return to normal operation mode.
Содержание ITC-608T
Страница 1: ...ITC 608T Manual...
Страница 6: ...4 TEMPERATURE Controller Manual Equivalent to ITC 308 Temperature Controller Manual ITC 608T Part 2...
Страница 7: ...5 86 8f 96 0f WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...
Страница 15: ...13 86 8f 96 0f WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...
Страница 28: ...26 DUAL TEMPERATURE PROBES Controller Manual ITC 608T Part 4...
Страница 29: ...27 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller 88 6f 98 6f...
Страница 38: ...36 HUMIDITY Controller Manual Equivalent to IHC 200 Humidity Controller Manual ITC 608T Part 5...
Страница 39: ...37 56 8 66 0 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...
Страница 46: ...44 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller 88 6f 56 8...
Страница 54: ...Inkbird Tech C L support ink bird com www ink bird com 86 755 25738050 Shenzhen GD 518000 China...