3.2 Setting Menu Instruction

Code 

Symbol 

Function 

Setting Range 

Default 

Settings 

Annotation 

TS 

tS

 

Temperature Setting 

Value 

-40.0

℃~

100

 

25.0

 

-40.0

~212

 

77.0

 

 

HD 

 

Heating Difference 

Value 

0.3

℃~

15.0

 

2.0

 

1.0

~30.0

 

3.0

 

 

CD 

 

Cooling Difference 

Value 

0.3

℃~

15.0

 

2.0

 

1.0

~30.0

 

3.0

 

AH 

AH

 

Alarm High 

Temperature Value 

-40.0

℃~

100

 

100

 

-40.0

~212

 

212

 

 

 

AL 

AL

 

Alarm Low 

Temperature Value 

-40.0

℃~

100

 

- 40.0

 

-40.0

~212

 

- 40.0

 

PT 

 

Compressor Delay

 

0

10 minutes  

0 minute 

More details on  4.3 

More details on  4.  

More details on  4.1

CA 

CA

 

Temperature 

Calibration

 

-9.9

℃~

9.9

 

0.0

 

More details on  4.4 

-15.0

~15.0

 

0.0

 

CF 

CF

 

Fahrenheit or 

Celsius  Setting

C or F 

More details on  4.5 

TR 

Timer Setting 

0

1 or 2 

More details on  4.6  

4  

 Control Function Instruction

When the controller works normally, the PV shows the 
measured temperature, meantime the SV screen shows the 
temperature setting value, and automatically recognizes and 
converts for the heating or cooling working mode , in which 
WORK1 is the heating output, furthermore the red led is the 
WORK1 heating output status indicator;WORK2 is cooling 
output, furthermore the green led is WORK2 cooling output 
status indicator.

4.1   Instructions for Setting Temperature Control 

(

TS,HD,CD

4.1.1 Normal Temperature Control

When the measured temperature PV ≤ TS(Temperature Setting 

Value) – HD(Heating difference value),the controller will enter 
the heating state, the red led is on, WORK1 output works. 

When the measured temperature PV ≥ TS(Temperature Setting 

Value), the red led is off and the WORK1 output turns off.

When the measured temperature PV ≥ TS(Temperature Setting 

Value) + CD(Cooling difference value), the controller will enter 
the cooling state, the green led is on, WORK2 output works; 
the green led flashes, indicating that the cooling device is in 
the state of the Compressor delay protection. When 

PV(measured temperature) ≤ TS(temperature setting value), 

H

 

C

 

   

P

 

 

.

2

Содержание ITC-608T

Страница 1: ...ITC 608T Manual...

Страница 2: ...d Into 6 Parts Part 2 Temperature Controller Manual Part 3 Programmable Temperature Controller Manual Part 5 Humidity Controller Manual Part 6 Humidity Temperature Controller Manual 1 4 12 36 Part 4 D...

Страница 3: ...ture Controller Manual PROGRAMMABLE TEMPERATURE Controller Manual Equivalent to ITC 310T B Temperature Controller Manual ITC 608T ITC 608T Temperature Control Mode ITC 608T Temperature Probe 2 Quick G...

Страница 4: ...ahrenheit Fahrenheit Error 40 T 10 2 40 T 50 3 10 T 80 1 50 T 176 2 80 T 100 2 176 T 212 3 Humidity Probe optional Type of humidity probe HTG3515CH Relative humidity measurement range 5 99 RH Humidity...

Страница 5: ...year from the date of purchase when operated under normal condition by the original purchaser not transferable against defects caused by INKBIRD s workmanship or materials This warranty is limited to...

Страница 6: ...4 TEMPERATURE Controller Manual Equivalent to ITC 308 Temperature Controller Manual ITC 608T Part 2...

Страница 7: ...5 86 8f 96 0f WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...

Страница 8: ...he function of compressor delay Yellow LED is on The controller is in the setting mode Button Instruction Please read the detail on 2 Button Operation Instructionsbelow Probe interface Temperature pro...

Страница 9: ...value and flashes and short press or button to increase or decrease the setting value long press or button to quickly increase or decrease the setting value nally press the SET button again to con rm...

Страница 10: ...rm High Temperature Limit Alarm Low Temperature Limit Compressor Delay Time Temperature Calibration Temperature Unit Press SET Key forover2 seconds to enterparameters setting mode TS 77 0 HD CD AH AL...

Страница 11: ...ature setting value and automatically recognizes and converts for the heating or cooling working mode in which WORK1 is the heating output furthermore the red led is the WORK1 heating output status in...

Страница 12: ...ate When PV measured temperature value 25 0 C the cooling stops Then return to normal temperature control When PV measured temperature value 25 0 C it enter the heating state when PV measured temperat...

Страница 13: ...on CA When the measured temperature deviates from the standard temperature the temperature calibration function can be used to make the measured value of the instrument consistent with the standard va...

Страница 14: ...12 PROGRAMMABLE TEMPERATURE Controller Manual Equivalent to ITC 310T B Temperature Controller Manual ITC 608T Part 3...

Страница 15: ...13 86 8f 96 0f WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...

Страница 16: ...he function of compressor delay Yellow LED is on The controller is in the setting mode Button Instruction Please read the detail on 2 Button Operation Instructions below Probe interface Temperature pr...

Страница 17: ...TR 1 or 2 Press PV shows current time unit SV shows the current remaining working time And It will be back to the normal display if there is no operation for 3 seconds or pressing the SET button Press...

Страница 18: ...press or to modify the setting value Press SET button again to con rm and exit If there is no operation for 3 seconds It will automatically exit after 10 seconds and save the setting value 2 5 Button...

Страница 19: ...Qty of stages depend on the STT Value Compressor Delay Time Stage12 Temperature Set Value Temperature Calibration Stage12 Duration Length Temperature Unit Stage12 User De ned Alert at the end of stag...

Страница 20: ...ture Setting Value 25 0 or 77 0 H03 H03 Stage 3 Control Duration Value 10 U03 U03 Whether to Alarm after the Completion of Stage 3 n S04 S04 Stage 4 Temperature Setting Value 25 0 or 77 0 H04 H04 Stag...

Страница 21: ...eating or cooling working mode in which WORK1 is the heating output furthermore the red led is the WORK1 heating output status indicator WORK2 is cooling output furthermore the green led is WORK2 cool...

Страница 22: ...to normal temperature control When PV measured temperature value 25 0 C it enter the heating state when PV measured temperature value 25 0 C heating stops and then return to normal temperature contro...

Страница 23: ...to make the measured value of the instrument consistent with the standard value The calibrated temperature the measured temperature the calibration value 4 5 Fahrenheit or Celsius Settings CF The use...

Страница 24: ...he temperature of the time period Regarding the difference between TR 1 Continuous Timer Mode and TR 2 Target Timer Mode the following table illustrates their differences in details Stage X N 1 12 STX...

Страница 25: ...the stage control time H01 H03 is only started when the current temperature reaches the setting temperature of the current stage such as 5 14 19 25 32 35 and total is 39 minutes 4 6 3 UT is a time un...

Страница 26: ...ately Press any button at this time to cancel the buzzer alarm and return to normal display If the cycle index MD is completed PV will show the current temperature and SV will show End 4 6 8 3 UX C If...

Страница 27: ...AT 1 Automatic Mode after the power is turned off the time still counts After the power is turned on again when TR 1 and UX X 01 12 is n or A the temperature controller will automatically calculate t...

Страница 28: ...26 DUAL TEMPERATURE PROBES Controller Manual ITC 608T Part 4...

Страница 29: ...27 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller 88 6f 98 6f...

Страница 30: ...mode the indicator LED is on otherwise off SV In normal mode the P2 measured temperature is displayed In setting mode it will display the setting value P2 Heating indicator LED If P2 Temperature Cont...

Страница 31: ...s in the setting mode Button Instruction Please read the detail on 2 Button Operation Instructionsbelow Probe interface Two temperature probes can be insert into P1 and P2 interface Temperature probe...

Страница 32: ...rease or decrease the setting value and then press SET again SV shows the temperature setting value of probe 2 and flashes at this time quickly press or button to increase or decrease the setting valu...

Страница 33: ...77 0 DS1 3 0 AH1 212 AH1 212 Heating or Cooling difference value STE Alarm High Temperature Limit STE Alarm Low Temperature Limit STE PT1 0Minute Working normally Compressor Delay Time STE CA1 0 0 Te...

Страница 34: ...9 9 9 9 15 0 15 0 100 212 40 0 40 0 0 minute 0 0 0 0 25 0 77 0 2 0 100 212 40 0 40 0 40 0 100 40 0 212 0 3 15 0 40 0 100 40 0 212 40 0 100 40 0 212 0 10minute 9 9 9 9 15 0 15 0 25 0 77 0 2 0 F H 3 0...

Страница 35: ...of Probe 2 When HC2 H the temperature mode is heating mode SV LED1 is on and when the measured temperature temperature setting value TS2 difference value DS2 it enters the heating state the WORK2 ind...

Страница 36: ...ternate AL2 with current temperature buzzer will bi bi Biii alarm until the tempera ture AL2 buzzer off and return to normal display and control Or press any button to turn the buzzer alarm off only 5...

Страница 37: ...heit or Celsius according to their habits The default temperature is Fahrenheit If you need to display the unit in Celsius then set the CF to C Please note that when the CF changes state all setting v...

Страница 38: ...36 HUMIDITY Controller Manual Equivalent to IHC 200 Humidity Controller Manual ITC 608T Part 5...

Страница 39: ...37 56 8 66 0 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller...

Страница 40: ...ng the function of compressor delay Yellow LED is on The controller is in the setting mode Button Instruction Please read the detail on 2 Button Operation Instructions below Probe interface Humidity p...

Страница 41: ...ty value and flashes and short press or button to increase or decrease the setting value long press or button to quickly increase or decrease the setting value and press the SET button again to con rm...

Страница 42: ...larm High humidity Limit SET Alarm Low humidity Limit Compressor Delay Time Humidity Calibration Press SET Key forover2 seconds to enterparameters setting mode HD 5 0 RH DD 5 0 RH AH 99 0 RH AL 5 0 RH...

Страница 43: ...humidi ca tion output status indicator WORK2 is dehumidi cation output furthermore the green led is WORK2 dehumidi cation output status indicator When PV measured humidity HS humidity setting value HD...

Страница 44: ...3 Dehumidifying Delay Protection Time PT In the dehumidifying mode when the power is turned on for the rst time it will not start dehumidi cation immediately when PV measured humidity value HS humidit...

Страница 45: ...TEMPERATURE HUMIDITY Controller Manual Equivalent to IHC 230 Temperature Humidity Controller Manual ITC 608T 43 Part 6...

Страница 46: ...44 WORK1 WORK2 A B C D E F P1 P2 1 Get to Know the Controller 88 6f 56 8...

Страница 47: ...e indicator LED is on otherwise off SV In normal mode the measured humidity is displayed In setting mode it will display the setting value Humidi cation indicator LED If humidity Control Function sele...

Страница 48: ...nstruction Please read the detail on 2 Button Operation Instructions below Probe interface Temperature or humidity probe can be insert into P1 or P2 Temperature humidity probe If the controller displa...

Страница 49: ...ckly increase or decrease the setting value Short press the SET button again SV shows the current humidity setting value and flashes and short press or button to increase or decrease the setting value...

Страница 50: ...AH AL PT 0Minute CA SET SET SET SET SET SET SET HC H No Key for 30 seconds or Presss SET key for over2 second Working normally T HS 50 0 RH DS 5 0 RH AH 99 0 RH AL 5 0 RH PT 0Minute CA 0 0 RH SET SET...

Страница 51: ...dicator LED to indicate whether the user has chosen humidi cation or dehumidi cation The WORK1 is output control of Temperature furthermore the red led is the WORK1 output status indicator the WORK2 i...

Страница 52: ...off and return to normal display and control Or press the button to turn the buzzer alarm off only When measured temperature AL low temperature limit alarm PV shows alternate AL with current temperatu...

Страница 53: ...are less than the delay time it needs to operate the remaining delay time to start dehumidi cation Delay time will start counting from the WORK2 output off 4 6 Temperature and Humidity Calibration CA...

Страница 54: ...Inkbird Tech C L support ink bird com www ink bird com 86 755 25738050 Shenzhen GD 518000 China...

Отзывы: