System Parameters

19

3.10.1Extinction times

The following parameters can be set on the extinction-
channel configuration page:

Automatic pre-extinction time

: duration of pre-

extinction time, in seconds, when triggered by fire-
fighting devices connected to the control panel.

Manual pre-extinction time

: duration of pre-extinction 

time, in seconds, when triggered by input devices 
programmed for manual-extinction (refer to following 
sections).

Valve Pulse

 (option 4.21 “Control of flooding time” of EN 

12094-1): duration of release time, in seconds.
Leaving the respective box 

[A]

 empty removes all time 

limitations.

3.10.2Trigger zones

The 

Zones

 button 

[B]

 accesses a screen that permits up to

three zones to activate the extinction phase when, within
one of the indicated zones, a certain number of alarms is
reached.

In order to select the zones, you must first activate one of
the three available options via the 

[D]

 check box, then tap

on the respective field at the side 

[E]

 to access the list of

configured zones. The arrow buttons 

[F]

 will allow you to

specify the number of alarms (maximum 3).

The image at the side shows how the system can be
configured so that the extinction channel is activated when
there are at least two alarms in zone 2.

3.10.3Extinction input

The 

Inputs

 button 

[C]

 will allow you to configure the control-panel input points to activate the extinction functions.

EN12094-1:

To ensure compliance with EN 12094-1, the inputs in use must be on-board I/O or supervised inputs on
loop modules (such as the EM312SR module).
It is not possible to connect more than 32 devices to each of the selected input terminals.
It is necessary to specify the input associated with the “Manual Extinction” function (the others are
optional).

These functions are grouped into the following categories:

• Activate

This section provides the extinction-activation parameters.

The parameters of the “Manual extinction” command allow
for the selection of an associated group (loop 1, loop 2 or
one of the “I/O” terminals 

[G])

, and the point 

[H]

 that

activates the release of the fire extinguishing agent in
accordance with the programmed pre-extinction time.

Selecting “--” for the group disables manual extinction on
the control panel.

000

Pre-ext. Automatic 
(sec)

Zones

000

Pre-ext. Manual 
(sec)

Inputs

Valve Pulse

300

(sec)

Esc

Set

Access level:3

A

B

C

Trigger zones

Requested Alarms

Zone 2

2

1

1

Esc

Set

Access level:3

D

E

F

Manual extinction

L 1

Button 1

Esc

Set

Access level:3

G

H

Содержание Previdia Compact

Страница 1: ...FIGURATION COMMISSIONING AND MAINTENANCE EN 54 2 EN 54 4 EN 54 21 EN 12094 1 ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL EXTINGUISHANT SYSTEM CONTROL PANEL ALARM TRANSMISSION AND FAULT WARNING ROUTING...

Страница 2: ...en goods or claims by any other party caused by defective products or otherwise arising from the incorrect or otherwise improper installation or use of this product This warranty applies only to defec...

Страница 3: ...figuring the Hornet network 13 3 5 Configuring the loops 13 3 6 SD card functions 16 3 7 Configuring the terminals 16 3 8 Configuring the users 17 3 9 Configuring the communicator 17 3 10 Configuring...

Страница 4: ...4 Table of contents Fire detection and extinguishant system...

Страница 5: ...scribes the procedures for the configuration commissioning and maintenance of the Previdia Compact fire detection system 1 2 1 Graphic conventions Following are the graphic conventions used in this ma...

Страница 6: ...ctivate alarm signalling when an early warning condition is running Level 2 Authorized users this access level is for the system supervisors and is for authorized personnel who are adequately instruct...

Страница 7: ...languages is required a mandatory main language and an optional second language The control panel screen will be as follows In the case of faults or other types of events the latter will be shown on t...

Страница 8: ...cess the programming phase of the Previdia control panel it is necessary to work through the following procedure 1 Insert the programming jumper see opposite D 2 Press the Programming button on the st...

Страница 9: ...to paragraph 4 2 Loop points refer to paragraph 4 1 Icon Function buttons Display Access to the configuration of the general parameters of the control panel Refer to paragraph 3 1 Access to the config...

Страница 10: ...onfiguration data on the Previdia Compact control panel can be done in two ways By selecting the Factory data option from the programming menu refer to paragraph 2 2 Using the buttons available on the...

Страница 11: ...tivated disables the control panel buzzer Direct alarm on second pre alarm option that if activated generates an alarm signal as soon as two detectors go into pre alarm status regardless of the zone t...

Страница 12: ...Installer Property option If activated the installer reserves the management of accesses to the system by the Cloud If not activated this property is assigned to the first user enrolled 4 Press the E...

Страница 13: ...e Esc and Set buttons will allow you to exit the section without changing the programming or saving it 3 5 Configuring the loops The operations for the configuration of the loops and the devices conne...

Страница 14: ...n in the columns on the left A and the newly detected configuration in the columns on the right B Positions in which changes have not been detected will be outlined in green Changes will be indicated...

Страница 15: ...in configuration The lower part C provides the following buttons Loop reset button to reset the loop and reassess its status In the event of a Loop open fault it will be necessary to tap on this butt...

Страница 16: ...SD card and there is the file Logo bmp file is the image contained in it 260x222 pixel will be shown on the stand by screen The Esc and Set buttons will allow you to exit the section without changing...

Страница 17: ...t control panels are supplied at default with the first 4 codes already pre set 3 9 Configuring the communicator To set the network parameters you must first enter the control panel programming phase...

Страница 18: ...rent from that detected by the control panel the appropriate icon inside the control panel configuration screen will change status and appear in yellow 3 9 1 Configuration of the PREVIDIA C COM module...

Страница 19: ...w the system can be configured so that the extinction channel is activated when there are at least two alarms in zone 2 3 10 3Extinction input The Inputs button C will allow you to configure the contr...

Страница 20: ...disables the programmed inputs for manual activation of the extinction procedure Disab Man Extinc option 4 23 Manual only mode of EN 12094 1 disables the automatic activation of the extinction proced...

Отзывы: