INIM Electronics Previdia Compact Скачать руководство пользователя страница 15

Configuration manual

System Parameters

15

After completing the connection of a new device or replacing an old device, it is necessary to select the address involved
then tap on the

 Add/Change

 button. When using Inim protocol, it is necessary to enter the serial number of the new

device.

-

Program

: button to access a section where it is possible to change some of the device options (refer to 

paragraph 

4.1 Loop point parameters

).

Once this operation has been completed the control panel will communicate with the new device. The appearance of
the type of device detected is the confirmation of its acquisition.

3.5.2 Loop diagnostics

The 

Diagnostics

 button in the Loop configuration menu accesses the section for the loop diagnosis.

The upper left side 

[A]

 shows some of the electrical data of

the loop.

Loop status

: indicates whether the loop is a closed ring 

circuit or open

Loop O Terminal

: indicates eventual short-circuits or 

anomalies immediately on the loop output terminals

Loop I Terminal

: indicates eventual short-circuits or 

anomalies immediately on the loop input terminals

Loop Consumption

: indicates the voltage draw of the 

loop

Cable resistance

: indicates the resistance value of the 

cable

The upper right side 

[B]

 shows the number and type of

devices currently in configuration.

The lower part 

[C]

 provides the following buttons:

Loop reset

, button to reset the loop and reassess its status.

In the event of a “Loop open” fault, it will be necessary to tap on this button in order to check whether or not the 
interruption has been cleared.

Scan

, button to start a scan on an already enrolled loop.

The procedure verifies whether there are any connected devices which are not in the configuration, if devices have 
been lost or if there are any other anomalies. The results of the scan can be viewed in the section on the top right of 
the display.

Show topology

, button which steps to the layout screen 

of the devices in the configuration of the already enrolled 
loop.

The layout shows all the devices which are connected to
the loop and how they are connected to one another.

Any devices in alarm or fault status will be outlined in red or
yellow 

[D]

.

The selection of a device accesses the management page
of the device itself

The 

Update

 

button 

[E]

 refreshes the screen by updating any

alarms and faults signalled by the devices shown (restored
fault events will not be shown).

Loopx: loop yyy

Loop status: closed
Loop O terminal: OK
Loop I terminal:
Loop consumption (mA): 15
Cable resistance (Ohm): 0

Generic: 1
Detectors: 44
IN Modules: 12
OUT Modules: 5
IN/OUT Modules: 0
Sounder/flashers: 3
Call points: 8

Rearm

Scan

Show topology

Esc

Access level:3

A

B

C

Update

Esc

Access level:3

001

002

003

004

005

006

007

008

D

013

014

015

016

017

E

023

024

025

D

Содержание Previdia Compact

Страница 1: ...FIGURATION COMMISSIONING AND MAINTENANCE EN 54 2 EN 54 4 EN 54 21 EN 12094 1 ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL EXTINGUISHANT SYSTEM CONTROL PANEL ALARM TRANSMISSION AND FAULT WARNING ROUTING...

Страница 2: ...en goods or claims by any other party caused by defective products or otherwise arising from the incorrect or otherwise improper installation or use of this product This warranty applies only to defec...

Страница 3: ...figuring the Hornet network 13 3 5 Configuring the loops 13 3 6 SD card functions 16 3 7 Configuring the terminals 16 3 8 Configuring the users 17 3 9 Configuring the communicator 17 3 10 Configuring...

Страница 4: ...4 Table of contents Fire detection and extinguishant system...

Страница 5: ...scribes the procedures for the configuration commissioning and maintenance of the Previdia Compact fire detection system 1 2 1 Graphic conventions Following are the graphic conventions used in this ma...

Страница 6: ...ctivate alarm signalling when an early warning condition is running Level 2 Authorized users this access level is for the system supervisors and is for authorized personnel who are adequately instruct...

Страница 7: ...languages is required a mandatory main language and an optional second language The control panel screen will be as follows In the case of faults or other types of events the latter will be shown on t...

Страница 8: ...cess the programming phase of the Previdia control panel it is necessary to work through the following procedure 1 Insert the programming jumper see opposite D 2 Press the Programming button on the st...

Страница 9: ...to paragraph 4 2 Loop points refer to paragraph 4 1 Icon Function buttons Display Access to the configuration of the general parameters of the control panel Refer to paragraph 3 1 Access to the config...

Страница 10: ...onfiguration data on the Previdia Compact control panel can be done in two ways By selecting the Factory data option from the programming menu refer to paragraph 2 2 Using the buttons available on the...

Страница 11: ...tivated disables the control panel buzzer Direct alarm on second pre alarm option that if activated generates an alarm signal as soon as two detectors go into pre alarm status regardless of the zone t...

Страница 12: ...Installer Property option If activated the installer reserves the management of accesses to the system by the Cloud If not activated this property is assigned to the first user enrolled 4 Press the E...

Страница 13: ...e Esc and Set buttons will allow you to exit the section without changing the programming or saving it 3 5 Configuring the loops The operations for the configuration of the loops and the devices conne...

Страница 14: ...n in the columns on the left A and the newly detected configuration in the columns on the right B Positions in which changes have not been detected will be outlined in green Changes will be indicated...

Страница 15: ...in configuration The lower part C provides the following buttons Loop reset button to reset the loop and reassess its status In the event of a Loop open fault it will be necessary to tap on this butt...

Страница 16: ...SD card and there is the file Logo bmp file is the image contained in it 260x222 pixel will be shown on the stand by screen The Esc and Set buttons will allow you to exit the section without changing...

Страница 17: ...t control panels are supplied at default with the first 4 codes already pre set 3 9 Configuring the communicator To set the network parameters you must first enter the control panel programming phase...

Страница 18: ...rent from that detected by the control panel the appropriate icon inside the control panel configuration screen will change status and appear in yellow 3 9 1 Configuration of the PREVIDIA C COM module...

Страница 19: ...w the system can be configured so that the extinction channel is activated when there are at least two alarms in zone 2 3 10 3Extinction input The Inputs button C will allow you to configure the contr...

Страница 20: ...disables the programmed inputs for manual activation of the extinction procedure Disab Man Extinc option 4 23 Manual only mode of EN 12094 1 disables the automatic activation of the extinction proced...